Search

Aspirating Smoke Detection for Data Centres (Class A)

Search

Data centres house critical IT infrastructure that stores, processes and manages digital information. They contain servers, network switches, power systems and cooling equipment arranged in rows or racks within controlled environments. Each component runs continuously, generating heat and drawing significant electrical load. Even minor faults can cause overheating or equipment failure.

Data centres are designed for uptime and continuity. Downtime leads to major financial loss, disrupted services and potential data corruption. Therefore, early fire detection is essential to prevent damage, limit downtime and protect both assets and personnel. Effective fire protection ensures operational continuity and compliance with industry standards.

Risks

Common fire risks in data centres include:

Electrical faults
Short circuits, overloaded circuits and component failures can create sparks or overheating that ignite nearby materials.
Overheating
High equipment density and restricted airflow can cause temperature rises in racks or under raised floors. Persistent heat can damage insulation and start fires.
Cable insulation failure
Ageing or damaged cabling can arc under load, generating localised heat that is difficult to detect early.
Cooling system faults
Loss of cooling or fan failure can lead to thermal runaway in servers and power supplies, increasing ignition risk.
Human error
Improper installation, poor maintenance or accidental obstruction of airflow can introduce unnecessary fire hazards.

Challenges

Designing effective fire detection for data centres involves several key challenges:

High airflow
Powerful cooling systems can disperse smoke before it reaches a conventional detector, delaying response times.
Equipment density
Tightly packed racks restrict airflow paths and limit detector placement, making uniform coverage difficult.
Early-stage detection
Most fires begin as overheating or smouldering components that produce minimal smoke, requiring highly sensitive detection.
Continuous operation
Fire systems must detect risk without causing false alarms that could trigger costly shutdowns or data loss.
Accessibility
Raised floors, ceiling voids and enclosed rack spaces are difficult to inspect or maintain, complicating sensor placement and servicing.

VESDA-E Aspirating Smoke Detection

VESDA-E is an advanced aspirating smoke detection (ASD) system designed for very early warning of fire in high-value environments such as data centres. It continuously draws air samples through a network of small pipes and analyses them using laser-based detection technology. This allows it to identify minute smoke particles long before they are visible or trigger a conventional detector.

The system uses active air sampling, ensuring constant monitoring even in areas with high airflow or limited access. It provides multi-level alarms for staged response, allowing investigation before suppression systems activate. Intelligent analytics and adaptive sensitivity enable reliable performance in both clean and contaminated air.

VESDA-E offers modular design, scalable coverage and simple network integration. It includes intuitive touch or remote interfaces for configuration and real-time status monitoring. The detectors feature high-efficiency aspirators, flow monitoring and built-in fault diagnostics. Connectivity options such as Ethernet, Wi-Fi and VESDAnet support integration with building management or fire alarm systems.

By combining precision detection with flexible configuration, VESDA-E delivers rapid, reliable fire warning while minimising false alarms. It provides the level of protection required for data centres classified as Class A, where downtime and data loss are unacceptable.

Class A

Class A ASD systems provide the highest sensitivity and earliest possible warning of fire. They are designed for critical environments such as data centres where even small amounts of smoke can indicate serious risk. Class A systems detect incipient fires in their earliest stages, allowing investigation and intervention before equipment or operations are affected. They meet strict performance standards for air sampling, detection speed and reliability.

Class B

Class B ASD systems offer early warning detection with slightly lower sensitivity than Class A. They are suited to areas where fire risk remains significant but not as critical, such as peripheral data hall spaces, power rooms or cable routes. Class B systems still provide fast and reliable smoke detection, ensuring prompt response while reducing the likelihood of nuisance alarms in less sensitive zones.

Class C

Class C ASD systems provide standard sensitivity detection for general areas where early warning is still beneficial but extreme sensitivity is unnecessary. They are typically used in support spaces such as offices, corridors or plant rooms within a facility. Class C systems balance dependable detection with reduced maintenance and lower installation cost while maintaining compliance with relevant fire safety standards.

VESDA-E VEP Aspirating Smoke Detector

VESDA-E VEP detectors deliver high-sensitivity aspirating smoke detection for critical environments. They use laser-based analysis and a powerful aspirator to detect the earliest signs of fire. Intelligent flow monitoring and adaptive calibration ensure accuracy in changing conditions. Each unit includes multi-level alarms, advanced diagnostics and simple network integration. VEP detectors provide fast, reliable warning with minimal maintenance, ideal for protecting Class A and B data centre areas.

VESDA-E VES Aspirating Smoke Detector

VESDA-E VES is an advanced aspirating smoke detector with built-in relay outputs for zoned fire response. It provides very early warning through continuous air sampling and laser-based analysis. The system supports up to four independently controlled alarm sectors, allowing precise shutdown or suppression actions. With adaptive flow control, network connectivity and simple configuration, the VES ensures fast, reliable protection in critical areas such as data halls and control rooms.

VESDA-E VES Group Shot

Approvals

VESDA-E systems are fully tested and approved to international fire detection standards, including EN54-20 for aspirating smoke detectors. These certifications confirm high sensitivity, reliability and compliance for use in life safety applications. The approvals ensure the systems meet stringent performance criteria required for critical environments such as Class A data centres.

Design Considerations

Control Panel Placement 

ASD for Data Centres VEP

VESDA-E panels can be installed in several ways to suit data hall layouts. A common approach is to mount a VES unit on a wall with sampling pipes routed above the server rows. This provides wide coverage and clear access for maintenance while drawing air from the hottest points near rack tops. 

Alternatively, a single-pipe VEP unit can be fitted directly onto a server wall, with the pipe extending into the racks for focused detection within equipment enclosures. 

Both configurations ensure fast smoke sampling, early warning and minimal disruption to airflow or cooling.

ASD for Data Centres VES

Pipe & Fittings Placement 

ASD for Data Centres pipe fitting

ASD pipe and fittings form the air sampling network that delivers continuous airflow to the detector. They are made from durable, low-friction material that maintains consistent pressure and flow rates across long runs. Pipes can be routed above, below or within server racks to suit the room layout. Proper joint sealing and even hole spacing ensure accurate smoke transport and fast response times. High-quality fittings and secure fixings help maintain system integrity and long-term reliability.

ASD for Data Centres pipe fitting

Low Level Maintenance 

Low-level maintenance is supported through the use of capillary pipes and accessible testing points.

Capillary pipes extend from the main ASD pipe network to low-level sampling points, allowing air to be drawn from critical areas without requiring access to high ceilings or confined rack spaces. Each sampling point is fitted with a precision orifice that ensures consistent airflow and smoke sensitivity across the system.

ASD for Data Centres pipe capillary

A dedicated testing point is installed at a convenient height, enabling functional testing and airflow verification without disturbing the main pipework. This allows maintenance teams to check detector performance quickly and safely from floor level, reducing service time and minimising disruption to operations.

ASD for Data Centres Testing point

Handpicked Solutions for Data Centres

Aspirating Smoke Detectors

VESDA-E VEP Aspirating Smoke Detector for Early Warning Fire Detection

VESDA VEP detectors use advanced Flair™ technology to give a very early warning of a potential fire while being smart enough to prevent false alarms. For ongoing accuracy and reliability, they are built with absolute calibration, protected internal optics, and an intelligent dust filter.

VESDA-E VES Aspirating Smoke Detector

The VESDA-E VES Aspirating Smoke Detector provides very early warning fire detection with built-in relays for zoned control. It continuously samples air through a pipe network and uses laser-based sensing for precise smoke analysis. With four configurable alarm sectors, it offers fast, targeted protection for critical environments like data centres.

Power Supplies and Batteries

VPS-220-STX5

The Xtralis VPS-220-STX5 is an EN54-4 certified power supply specifically designed for VESDA-E detectors. It delivers a continuous 0.5 A 24 V DC supply and charges standby batteries up to 14 Ah, providing a fully integrated and reliable power source for the entire system.

VPS-250-STX5

The Xtralis VPS-250-STX5 is a high-capacity power supply unit, fully certified to EN54-4 and engineered for larger or more demanding VESDA-E systems. It provides a robust, continuous 3 A 24 V DC output and features an integrated charger for standby batteries up to 24 Ah, guaranteeing reliable primary power and extended standby autonomy.

Aspirating Pipe & Fittings

VESDA Red ABS 25mm Pipe

This 25mm red ABS pipe is purpose-built for use in aspirating smoke detection installations.

VESDA Red ABS 25mm Socket

Use these sockets to connect two lengths of pipe, securing the join with an application of ABS solvent cement.

VESDA Red ABS 25mm 90° Tee

The 90° tee fitting is used to create a perpendicular branch from a main pipe run.

VESDA Red ABS 25mm 45° Elbow

The 45° elbow fitting is used to create a gradual change in direction, enabling pipework to navigate around obstacles.

VESDA Red 25mm Flexible Connector

Flexible connectors are used in place of standard elbows for awkward angles or tight spaces. Strengthened with an internal steel wire for durability, they can be mounted in any direction without restricting airflow.

VESDA Red ABS 25mm 90° Sweeping Bend

This 90° sweeping bend fitting alters the direction of a pipe run while preserving system integrity by minimising air loss.

VESDA Red ABS 25mm x 3/4″ Pipe Clip

This pipe clip securely holds air-sampling pipe with a quick-clamp action for simple installation, while optional fixing nuts and side rod connectors provide greater flexibility for more demanding mounting scenarios.

Sampling Point Kits, Sampling Points & Accessories

VESDA Flush Sampling Point

The Flush Mount Sampling Point is an advanced alternative to standard conical points for Xtralis ASD systems, offering significant improvements in both functionality and appearance.

VESDA Flush Air Sampling Point

This flush sampling point connects to a 10mm capillary pipe to provide a discreet finish. For versatile mounting, it can be fastened to a ceiling tile with the included nut or screwed directly into a solid ceiling.

Red 25mm Flush Capillary Kit

The Red 25mm Flush Capillary Kit provides discreet, low-level sampling points for ASD systems, ensuring accurate airflow and easy maintenance.

Air Sampling Labels

These self-adhesive, red air sampling labels are used to clearly mark and identify sampling points, and are supplied on convenient rolls of 100.

Why Choose Eurofyre?

Honeywell Fire Platinum Partner
As a Honeywell Fire Platinum Partner, Eurofyre is recognised for its capacity to deliver tailored solutions for specific regions and industries. This includes comprehensive implementation, advanced customer support, and preferential pricing for Honeywell products.
Complete System Supplier
Eurofyre is a complete system supplier with a long-standing partnership as a major Xtralis technical wholesaler, established in 2007. This long-standing expertise allows us to provide specialist advice and supply all aspects of fire detection, from aspirating smoke and linear heat systems to conventional and addressable control panels.
Pipework Design
Our services also include professional design support for aspirating pipe networks, helping clients achieve maximum system performance and a quality installation.
Demonstration and Training
Eurofyre delivers expert training and system demonstrations from our sophisticated facility, covering a wide range of products including VESDA VEP, VLF, amongst other aspirating smoke detection systems.
After-Sales Support
At Eurofyre, we are dedicated to delivering superior after-sales support. You can rely on our on-site and telephone assistance to keep your system fully functional and performing flawlessly.

For more information on VESDA aspirating smoke detection or to explore our full range of products, please contact us by phone on +44 (0) 1329 835 024, by email at sales@eurofyre.co.uk, or via the enquiry form on our contact page.

Don’t forget to follow us on LinkedIn, Bluesky and Instagram or sign up to our newsletter (in the footer below) to receive all the latest information from Eurofyre.