Key Features
- Permissible temperature range: –30 °C to +60 °C
- Immune to disturbances such as dust, dirt, moisture and steam
- Reliable detection in difficult environments
- Protection against false alarms
- Simple to integrate into existing architecture
Overview
Aspirating smoke detectors from Securiton are among the most reliable early warning systems for fires.
The Securiton ASD range of Aspirating Smoke Detectors have one of the most powerful fans on the market with over 400 pascals of aspirating under pressure. It is ideal for use in harsh environments such as deep-freeze areas, explosion hazard areas or rooms with high levels of contamination.
The Securiton ASD 533 is a highly sensitive aspirating smoke detection system. Based on the successful Securiton ASD 535 detector, the ASD 533 is well suited for smaller applications, applications with restricted access such as EDP rooms, ultra-clean-rooms, laboratories and prison cells, or in any area where ultra-rapid detection is required such as data centres.
Securiton aspirating smoke detectors are housed in a modern IP54 enclosure and can be configured and serviced from the fire alarm control panel thanks to the “Config over Line” function.
Area Coverage
Securiton ASD 533 aspirating smoke detector can cover areas up to 1920m2.
EN54-20 Aspirating Smoke Detection Sensitivity Classes
Securiton ASD 533 can provide sensitivity Class A, B or C detection.
Sensitivity Class | Number of sampling apertures per smoke sensor |
Class A | 16 |
Class B | 50 |
Class C | 50 |
Pipe Lengths
The Securiton ASD 533 supports two pipe networks with a maximum length of up to 200m.
Orientation
The Securiton ASD 533 can be rotated so that the pipe inlets can exit towards the ground or from the top to the ceiling.
Indication
The ASD 533 offers a standard LED display with Alarm, Fault and dusty or dirty indication, and a reset and power button.
Turntable
Approvals
VdS, FM, UL, UKCA, and CE are certifications marking compliance with safety and quality standards globally. VdS and FM focus on fire safety, UL offers broad safety certifications, UKCA signifies UK standards post-Brexit, and CE indicates a product meets essential EU health, safety, and environmental requirements.
Tech Specs
Supply voltage range | EN 54: 10.5 to 30 VDCFM/UL: 12.4 to 27 VDC |
Power consumption | 270 mA |
Suction pressure | > 400 Pa |
Sound pressure level | > 34 dB (A) |
Housing | IP 54 |
Alarm sensitivity | Alarm: 0.02 to 10%/m Pre-signal: 0.002%/m to 9%/m |
Alarm levels | 5 (3 pre-signals, alarm, alarm 2) Adjustable pre-signals 10 to 90% |
Relays | ASD 533-1: 3 (Pipe 1 Alarm, Programmable Relay, Fault) ASD 533-2: 3 (Pipe 1 Alarm, Pipe 2 Alarm, Fault) |
PC tool | USB |
Inputs | Reset, day/night |
Downloads
Datasheet
Brochure
Manuals
Approvals
- Securiton ASD 533 Certificate of Constancy of Performance
- Securiton ASD 533 VdS Certificate
- Securiton ASD 533 FM Certificate
- Securiton ASD 533 UL Certificate
- Securiton ASD 533 Declaration of Conformity
- Securiton ASD 533 Declaration of Performance
Buy
Contact us to receive competitive trade discounts or apply online for a credit account.