- 868 – 870 MHz Operating Frequency
- Up to 30 field devices per transponder
- 5 modes of operation
- Low operating current
- Optional PC configuration
Overview
The Wi-Fyre Transponder has been designed to communicate with up to 30 mixed field devices such as smoke and heat detectors, manual call points, sounders and LED indicators, and input/output devices.
There are two versions with or without LCD indication.
The Wi-Fyre Transponder is small and easy to install. Commissioning is accomplished either using an inbuilt 5 button plus LCD panel front display, or via an optional Wi-Fyre PC interface card connected to a PC or laptop.
Approvals
Wi-Fyre is approved by TUV for safe use and installation in any European Union country and bears the CE mark to show that it complies with all the applicable Directives including the CPR, EMC and the Low Voltage Directive (LVD).
- EN54-25:2008
Fire detection and fire alarm systems – components using radio links.
Tech Specs
Operating Frequency | 868 – 870 MHz, 14dBm |
Operating Channels | 28 |
Field Devices (max) | 30 per transponder |
Range | 150m open area |
Power Source | Addressable Loop, Conventional Zone and/or Auxiliary |
Display | None or LCD |
Local Control (optional) | 5 Tactile push-buttons or PC connection |
Zone In/Out Ratings | 19 – 24Vdc, 400mA |
Zone In/Out Terminal Alarm Resistance | Equivalent to 450 Ohm |
Sounder In/Out Ratings (max) | 8 – 24Vdc, 800mA |
Auxiliary Supply Voltage (max) | 19 – 40Vdc |
Manual Alarm Relay Contact | 1 x Solid-state normally open, 60Vdc, 600mA |
Automatic Alarm Relay Contact | 1 x Solid-state normally open, 60Vdc, 600mA |
Common Fault Contact | 1 x Solid-state normally closed (failsafe), 60V, 500mA |
Cable Terminals | Rising clamp 1.5mm |
Operating Current (nom.) | 12mA |
Configuration Interface | Local and/or Wi-Fyre PC interface |
Operating Temperature | -10 to +55°C |
Ingress Protection | IP54, for Indoor use only |
Humidity | 10 to 95% RH (non-condensing) |
Dimensions (Width x Height x Depth) | 234 x 164 x 75mm |
Weight | 620g |
Housing Material | Polycarbonate |
Colour | White |
Cable Entries | 6 x 20mm |
Applicable Standards | EN54-25, BS 5839 Part 1:2002, ENTSI 300:220 |