Key Features

  • Monitors the ambient environment
  • Cancels common mode signals
  • 3 Reference Sensors per controller 
  • Colour coded connection
  • Mounting bracket supplied

Overview

This product has been discontinued and has been replaced by the Li-ion Tamer Reference Sensor, Gen 3. Please contact Eurofyre further information, spare parts, servicing and training.

The Li-ion Tamer Rack Monitoring System detects off-gas events that occur in the early stages of lithium-ion battery failure. By detecting these events, hazards can be investigated and dealt with before thermal runaway occurs and flames and smoke cause any damage to surrounding equipment.

Li-ion Tamer rack monitors consist of three key components; a control panel, monitoring sensors and reference sensors. 

Monitoring sensors are installed into the battery rack to monitor for off-gas events, while reference sensors are distributed throughout the area around the battery racks to  monitor the ambient environment and air inlets, such as HVAC exchangers and doors, so the can system cancel common mode signals.

Reference sensors should be installed in areas such as any entrance or exit locations to the battery space, including doors and access points, and any possible gas entry points, such as forced or passive vents and unsealed gaps.

Multiple points that are identified on one surface can be monitored with one reference sensor and up to 3 reference sensors can be used with each controller. All reference sensor cables and their associated ports are blue to provide easy installation and reduce the risk of improper connection.

Reference sensors can be mounted by either creating a hole through the panel the sensor is to be mounted on or using the supplied mounting bracket. 

Approvals

Li-ion Tamer Reference Sensors are ETL listed to UL61010 and CSA22.2 No. 61010, are EN 61326 for EU Directive (2014/30/EU) and are RoHS 3 EU 2015/863 compliant.

Tech Specs

Sensor DimensionsØ 28.6mm x 25.4mm
Monitor Cable Length25ft
50ft
100ft 
Wire TypeBrown (POWER +)
Green/White (GND)
Brown/White (SIGNAL +)
Operating Temperature-10 to +60°C
Storage Temperature-10 to +70°C 
Humidity5 to 95% RH 
Max Temperature Change8.6°C/min 
Controller Power Input3 – 16 VDC
Power Consumption275 mW (@ 5VDC and 25°C)
Output Signal (error state)0.10 VDC 
Output Signal (warm up)0.25 VDC
Output Signal (OK)0.50 VDC
Output Signal (alarm)3.0 VDC 
Target GasesLithium-ion battery electrolyte solvent vapors
Min. Detection Threshold<1 ppm/sec
Response Time5 seconds
Fault DetectionSingle cell failure
Target Lifetime10 years
Warranty1 year
Product SafetyUL/IEC 61010
EMCEN 60326-1 for EU Directive (2014/30/EU)
RoHSRoHS 3 EU 2015/863

Downloads

Buy

Eurofyre is an authorised distributor of Honeywell and has been a major technical wholesaler of Xtralis products since 2007. We offer expert advice and supply all aspects of Li-ion Tamer lithium ion detection systems including excellent before and after-sale support.

Contact us to receive competitive trade discounts or apply online for a credit account.

This product has been discontinued and has been replaced by the Li-ion Tamer Reference Sensor, Gen 3. Please contact Eurofyre further information, spare parts, servicing and training.