Smoke Detection in High Ceiling Applications Using ASD

2 mins read

For many years high ceiling applications have been considered very challenging for reliable operation of automatic point smoke detection. Many national design and installation codes, including BS5839 Part 1, specify limitations on ceiling heights that are protected by a particular product technology.

As a result designers and installers tend to use detection technologies such as beam detection and aspirating smoke detection (ASD) where smoke measurements over an area, rather than from a single location, are determined. Independent tests have shown that ASD has a far higher sensitivity to smoke than point detector technology, resulting in a superior ability to detect smoke that is diluted or distributed as it rises to higher levels.

In 2008 BRE (Building Research Establishment) Global, whose remit is to work with manufacturers to ensure that fire, security, environmental and other products and services provide quality of performance and protection, completed a three-part research project (together with the Fire Industry Association) to review the use of beam detection and ASD technology in high ceiling applications.

The positive tests that came out of this process resulted in the FIA Code of Practice for ASD being revised. This was largely due to the high sensitivity ASD needs to support multiple holes and the cumulative effects that result from smoke entering a number of sampling holes.

The research confirmed that ceiling height limits for aspirating smoke detection should be based on those for beam detection (which is used at heights of 25m or 40m for property protection) on the provision that Fire Rescue Services can attend within 5 minutes. Other independent tests have confirmed that a Class C aspirating smoke detection system with 20 sampling holes at a height of 43m can detect relatively small fires (<500kW). For detailed information and recommendations, refer to the FIA code of practice.

Suitable Aspirating Smoke Detectors for High Ceiling Applications

Many of the ASD systems Eurofyre supply and support operate at Class A, B & C sensitivity depending on the amount of designed sampling holes, an example of which is the EF-FT1.

The EF-FT1 is a 4-pipe detector that can cover a single zone of up to 2000m². It is classified as a very early warning smoke detector and has the ability to reliably detect fire at an early stage with an alarm sensitivity range of 0.001% to 20% obscuration/m (0.0003% to 6.10% obscuration/ft).

Key Features

  • EN54-20 approved
  • 4-pipe air-sampling
  • Single zone
  • Area coverage up to 2000m²
  • 0.001% to 20% obscuration/m
  • 4 alarms – Alert, Action, Fire 1, Fire 2
  • 4 x 100m (max) sampling pipes
  • 5 relay outputs as standard
  • Optional internal power supply and batteries

For more information please visit the aspirating smoke detection section on our website, alternatively, please do not hesitate to get in touch either by email to [email protected], by telephone on 01329 835 024 or through our online enquiry form.

    Contact Eurofyre

    FireRay Hub Beam Detection in Churches

    21st October 2026

    FireRay Hub Beam Detection in Churches

    Churches and cathedrals are among the most historically and culturally significant buildings in the UK. Alongside their primary role as places of worship, they regularly host weddings, funerals, concerts, community events and visitors, and many also house irreplaceable artefacts, artwork, organs and archives. Many of these buildings are centuries old, listed, and built with substantial […]

    Read Article
    SMS SenTRI Addressable Fire Detection for Student Accommodations

    14th October 2026

    SMS SenTRI Addressable Fire Detection for Student Accommodations

    Student accommodation ranges from traditional university halls of residence to large purpose-built complexes operated by private providers. These buildings typically combine individual bedrooms or studio flats with shared kitchens, lounges, study areas and laundry facilities, and are occupied by large numbers of residents throughout the day and night. Effective fire detection is essential in these […]

    Read Article

    30th September 2026

    SecuriSmoke ASD 2000 for Hospitals

    Hospitals are among the most complex buildings in the built environment, combining wards, operating theatres, diagnostic imaging suites, laboratories, plant rooms, pharmacies and administrative offices within a single site that typically operates around the clock. They accommodate patients with varying levels of mobility, alongside clinical staff, visitors and contractors, often across multiple interconnected buildings of […]

    Read Article
    • FyreLine Linear Heat detection
    • Crisis Emergency Voice Communication
    • Xenos Wireless Fire Detection

    Eurofyre is proud to supply its own brands to the fire detection and safety market. All of our products are high quality, extremely reliable and cost-effective.

    Sales & Technical Support

    Eurofyre Sales and Technical Support

    Accreditations

    ISO 9001
    UKAS Management System
    Fire Industry Association
    British Chamber of Commerce