Crisis Type B Refuge Outstation

POA

Crisis Type B Refuge Outstation

POA

Crisis Type B Refuge Outstation

POA
  • Fully compliant to BS5839-9:2011
  • Designed and manufactured in the UK
  • Hands free operation
  • High volume ringer
  • LED and Braille enhanced call button

Learn about the Crisis Type B Refuge Outstation in the

Eurofyre Knowledge Base
Part Number: 36-301 Category: Brand:

Learn about the Crisis Type B Refuge Outstation in the

Knowledge Base

Description

The Crisis Type B Refuge Outstation is a crucial component of an Emergency Voice Communication System (EVCS), engineered to fully comply with BS5839-9:2011. An EVCS provides a vital fixed, secure, bi-directional voice communication link, assisting firefighters in high-rise buildings or large sites where traditional radio communication might be compromised. These systems are designed to function as fire telephones, disabled refuge systems, or a combined solution.

Specifically, the Type B Outstation is intended for public use as a disabled refuge call point, adhering to the definitions within BS5839-9:2011. It must be located in designated disabled refuge areas, in accordance with Building Regulations Approved Document B and BS9999:2008. Manufactured in the UK, the unit features hands-free operation, a high-volume ringer, and an LED and Braille-enhanced call button for improved accessibility. Its brushed stainless finish and a green flashing button further aid location.

The outstation is compatible with Crisis standalone and network EVCS. For installation, it requires an ‘MK’ style double back-box, with a minimum depth of 25mm, or 35mm if cable glands are used. To comply with Building Regulations Document M for disabled access, the unit should be mounted with its centre line between 900mm and 1200mm from the finished floor level. An adjacent sign is to be placed providing instructions and identifying the call point.

Learn more about becoming an Authorised Crisis EVC Distribution Partner HERE.

Additional information

Weight12 kg
Dimensions22 × 22 × 22 cm
Application

Commercial, Education, Government, Healthcare, Heritage, Hospitality, Industrial, Information Technology, Leisure, Office, Public Buildings, Residential, Retail, Transport

Colour

Silver

Country of Origin

United Kingdom

Environment

Indoors

HS Code

8531103000

Material

Stainless Steel

Mounting

Semi-flush, Surface

Product

Disabled Refuge Outstation

Protocol

Open Protocol

Standards

BS 5839-9, BS 8893, BS 9991

System

Emergency Voice Communication

System Category

Coventional

System Protocol

Crisis EVC Network, Crisis EVC Standalone

Wiring

Radial

Unit

Piece