ProFyre C24 Conventional Fire Alarm Panel

POA

ProFyre C24 Conventional Fire Alarm Panel

POA

POA
  • Approved to EN54-2 & 4
  • 8, 16, 24 zone versions
  • 4 monitored sounder circuits
  • Expansion of zone and sounder circuits
  • Repeater panel output

Learn about the ProFyre C24 Conventional Fire Alarm Panel in the

Eurofyre Knowledge Base
Part Number: 13-010-P Category: Brand:

Learn about the ProFyre C24 Conventional Fire Alarm Panel in the

Knowledge Base

Description

The ProFyre C24 Conventional Fire Alarm Panel, though now discontinued, was a flexible and expandable modular system offered in 8, 16, or 24 zone versions. Designed for straightforward installation, commissioning, maintenance, and operation, it provided high standards of quality and reliability. Its metal enclosure allowed for surface or semi-flush mounting, ensuring excellent access during setup.

The panel incorporated four monitored sounder circuits and a SELV fault and fire relay, with modular PCB cards enabling further expansion of zones and sounder circuits. It was compatible with a full range of ProFyre conventional field devices, supporting up to 32 devices per zone. The C24 held comprehensive approvals, including EN54-2 and EN54-4, and bore the CE mark from Intertek, confirming compliance with all applicable EU directives.

Technical specifications included a 21Vdc nominal zone voltage, 150mA sounder alarm outputs, and a 5A total PSU output. It was designed to accommodate two 12V 17Ah SLA batteries and functioned within an operating temperature range of 0° to +50°C.

Additional information

Alarm Identification

Common Identification, Zonal Identification

Application

Agricultural, Commercial, Education, Government, Healthcare, Heritage, Hospitality, Industrial, Information Technology, Leisure, Office, Public Buildings, Residential, Retail, Transport

Approval Body

Intertek

Battery Capacity

2 x 17Ah

Cable Entries

26

Colour

Grey

Country of Origin

United Kingdom

Devices

32∣64∣96∣128∣160∣192∣224∣256∣288∣320∣352∣384∣416∣448∣480∣512∣544∣576∣608∣640∣672∣704∣736∣768

Environment

Indoors

HS Code

8531103000

Input Voltage

230VAC

IP Rating

IP30

Material

Steel

Mounting

Semi-flush, Surface

Networkable

No

Product

Fire Alarm Control Panel

Programming

On-board

Protocol

Open Protocol

Standards

EN54-2, EN54-4

System

Fire Detection

System Category

Conventional

System Protocol

Conventional

Wiring

Radial

Zones

16, 24, 8

Relays

2

Detection Architecture

Independent

Unit

Piece

Indication

LED