Key Features

  • Quickly simulate fault and alarm conditions
  • Secure, weatherproof enclosure 
  • Provides a simple and straightforward method to carry out a functional test on the system
  • Supplied with 2 IP67*1 rated cable glands
  • EN54-28:2016 approved

Overview

The FyreLine EN54 Fixed End of Line is designed to effectively terminate up to two zones of FyreLine EN54 Fixed linear heat detection cable in a secure, weatherproof enclosure. It has built in switches to simulate fault or alarm conditions to allow the system to be fully tested in situ.

The FyreLine EN54 Fixed End of Line is particularly suitable for when the system is used in interlock mode to prevent false alarms. In this mode, two fixed LHD cables are run side-by-side and an alarm is only activated on the fire alarm control panel when both cables trigger. 

Turntable

Approvals

EN54-28 is the European Standard for non-resettable line-type heat detectors that consist of a sensing element that uses electrical sensor cable. It specifies the requirements and performance criteria; and the corresponding test methods. This European Standard also covers non-resettable line-type heat detectors intended for use in the local protection of plant and equipment.

Please note: to comply with EN54-28, the FyreLine EN54 Fixed Controller, FyreLine FyreLine EN54 Fixed EOL and FyreLine EN54 Fixed LSZH LHD Cable must be used as a complete system.

All products in the FyreLine EN54 range are approved for use within the European Economic Area (EEA) and comply with the EU’s New Approach Directives and show the CE mark to indicate that they fulfill the requirements of relevant European product directives; meet all the requirements of the relevant recognized European harmonized performance and safety standards; and are fit for purpose and will not endanger lives or property.

Tech Specs

ConstructionIP66*1 Rated Enclosure supplied with 2 IP67*1 Rated Cable Glands
Dimensions (W x H x D)94mm x 94mm x 57mm
ApprovalsEN54-28:2016
Environmental GroupII
UL Model NumberFLDEOL-EN54
UL File NumberS36489
End of Line Terminal Blocks2 x 5mm Rising Clamp
LHD Cable Terminal Blocks2 x Removable Header 5mm Rising Clamp
Ambient Temperature Rating-35oC to +55oC*2

*1 Outside the scope of EN54-28:2016, not verified by UL.
*2 Verified by UL to EN54-28:2016 Environmental Group II between -10°C to +55°C.

Downloads

Buy

Eurofyre is a global provider of specialist fire detection and associated safety products for commercial and industrial applications. The systems we manufacture, supply and promote are designed to give users time to respond to possible threats before the loss of critical infrastructure, high-value assets, business and, most crucially, life. Eurofyre has designed, supplied, delivered, and provided comprehensive training on Linear Heat Detection systems for a huge variety of applications over the last fifteen years. 