Key Features

  • UL 521 approved and compliant with the EN54:22 draft standard
  • Self-restorable analogue type system with optional pre-alarm setting
  • Cable based sensing allows detection at the point of risk
  • Low installation, maintenance and repair costs
  • Reliable solution for hazardous areas

Overview

Stainless steel braiding over the outside of the FyreLine cable provides the ideal solution for areas where the cable may be accidentally cut or where it may be subject to mechanical abrasion.

Sensing Cable Construction

FyreLine Analogue Linear Heat Detection cable is constructed using a pair of copper conductors coated in a temperature sensitive polymer whose resistance changes as a function of temperature. A calibration resistance (white) and average ambient temperature sensor (red) core are also twisted with the two original conductors. A foil shield and protective outer coat is extruded over the twisted core.

Approvals

The FyreLine analogue linear heat detection cables are fully approved by the Underwriters Laboratories (UL) and bears the CE mark to show that they comply with all the applicable Directives including the CPR, EMC and the Low Voltage Directive (LVD).

  • UL 521
    Heat detectors for fire protective signaling systems.

Tech Specs

Outer JacketStainless Steel Braided
Overall Diameter4.57mm ± 0.075mm (0.180” ± 0.003”)
Humidity0% to 99% RH
RFI ShieldingTwisted and foil shielding to reduce inductance and RF susceptibility
CoresCalibration Resistance: White
Sensor Core: Red
Conductor & Specially Doped Polymer Core: Clear
Conductor & Specially Doped Polymer Core: Clear
Maximum Continuous Length500m (1640ft)
Minimum Continuous Length30.5m (100ft)
Operating Temperature Range-40ºC to 125ºC
Continuous Ambient Temperature Range-40ºC to 90ºC

Downloads

Buy

Analogue LHD Cable, SS Braided, 54°C – 100°C, 100m

18-240
POA
Contact Us

Analogue LHD Cable, SS Braided, 54°C – 100°C, 200m

18-241
POA
Contact Us

Analogue LHD Cable, SS Braided, 54°C – 100°C, 500m

18-242
POA
Contact Us