Key Features

  • Compatible with FyreLine analogue systems
  • Nylon and PVC outer jacket available
  • Non-sensing, used as an interpose solution
  • Low installation, maintenance and repair costs
  • Reliable solution for hazardous areas

Overview

FyreLine Non-Sensing Leader/Interposing Cable is used to bridge the gap between the heat sensing cable and the FyreLine control module. FyreLine Non-Sensing Leader Cable is easy to install, low-maintenance and cost-effective and is compatible with all FyreLine analogue linear heat detection systems.

In the case that the control module is not installed near to the protected area, non-sensing leader cable can reliably and cost-effectively carry the signal from the FyreLine heat sensing cable to the interface module. This is particularly useful, for example, in applications where the area to be protected has hazardous properties that may be harmful to the interface module.

FyreLine Analogue Non-Sensing Leader Cable is manufactured to the same specifications as the sensing cable and provides accurate resistance readings to ensure that the FyreLine detection system operates effectively.

There are two leader cable coating options available to ensure that the cable meets the requirements of the environment:

  • White PVC coating – Suitable for most normal indoor and outdoor environments.
  • Black Nylon coating – Suitable for harsh outdoor environments, hazardous areas where hydrocarbons are present or where the cable is exposed to UV rays.

Hazardous Area Limitations

In the case of Gas Group IIC applications, the limiting factor on zone lengths is due to the FyreLine analogue red core inductance. In the case of Gas Group IIB and IIA applications, the limiting factor on zone lengths is the maximum allowed sensor cable per controller.

Figures below are on the basis that Zenner barriers are used in conjunction. Contact Eurofyre for further information.

Gas GroupFyreLine Analogue Cable Arrangements
IICOnly Analogue Linear Heat Detection Cable: 275m
With 100m Non-Sensing Leader Cable: 241m
With 250m Non-Sensing Leader Cable: 191m
IIBOnly Analogue Linear Heat Detection Cable: 500m
With 100m Non-Sensing Leader Cable: 500m
With 250m Non-Sensing Leader Cable: 500m
IIAOnly Analogue Linear Heat Detection Cable: 500m
With 100m Non-Sensing Leader Cable: 500m
With 250m Non-Sensing Leader Cable: 500m

Tech Specs

Outer JacketWhite PVC (for non-hazardous areas)
Black Nylon (for hazardous areas)
Overall DiameterPVC – 6.30mm (0.248”)
Nylon – 7.50mm (0.295”)
RFI ShieldingFoil shielding to reduce inductance and RF susceptibility
Cores4
Capacitance<150pF/m
Inductance<2μH/m
L/R Ratio<30μH/Ω
Resistance~0.035Ω/m

Downloads

Buy

Analogue Non-Sensing Leader Cable, PVC, 100m

18-280
POA
Contact Us

Analogue Non-Sensing Leader Cable, PVC, 250m

18-281
POA
Contact Us

Analogue Non-Sensing Leader Cable, PVC, Nylon, 100m

18-282
POA
Contact Us

Analogue Non-Sensing Leader Cable, PVC, Nylon, 250m

18-283
POA
Contact Us