Key Features

  • Approved to EN54-2 & 4
  • 8, 16, 24 zone versions
  • 4 monitored sounder circuits
  • Expansion of zone and sounder circuits
  • Repeater panel output

Overview

The ProFyre C24 conventional fire alarm panel has been discontinued. Please contact us below for an alternative modular fire alarm panel.

A flexible, fully-featured expandable modular based conventional fire alarm control panel available in 8, 16 or 24 zone versions. The panel provides a high standard of quality and reliability that is easy to install, commission, maintain and simple to operate.

The metal enclosure can be surface or semi-flush mounted and provides excellent access during the installation and commissioning stages. 4 monitored sounder circuits and a SELV fault and fire relay are included with further expansion options for zones and sounder circuits using the modular based expansion PCB cards.

ProFyre Conventional Devices

Complemented by a complete range of ProFyre conventional field devices, the ProFyre C24 is the logical choice for systems that require clear alarm management and ease of use.

Mounting Options

The ProFyre C24 has been designed to accommodate for many applications. Available in 2 versions; surface or semi-flush.

Approvals

The ProFyre C24 is fully approved by Intertek for safe use and installation in any European Union country and bears the CE mark to show that it complies with all the applicable Directives including the CPR, EMC and the Low Voltage Directive (LVD).

  • EN54-2:1997+A1:2006
    Fire detection and fire alarm systems – Control and indicating equipment.
  • EN54-4:1997+A1:2002+A2:2006
    Fire detection and fire alarm systems – Power supply equipment.

Tech Specs

Zones8, 16, 24
Device 32 per Zone
Zone Voltage 21Vdc Nominal
Zone Short Circuit Protection 100mA
Zone End of Line Device 1N4002 Diode
Manual Call Point Trigger Resistance 470 Ohm or 680 Ohm
PanelSounder Delay
One Man Test Facility
Zonal & Sounder Isolation
IndicationPower, Common Fire, Common Fault, Supply Fault, Earth Fault, System Fault, General S/C, Sounder Fault Disablement, Sounder Delay, F.A.R.E Active, F.A.R.E Fault Disablement, Repeater Fault, General Disablement, General Test, Controls Active, Zone 1-24 Fire, Zone 1-24, Fault, Zone 1-24 Test/Disabled
ControlsPanel Access, Start/Stop Sounders, Silence Buzzers, Reset, LED Test, Sounder Delay, Function, Scroll, Select
Outputs1 x VFCO Fault Relay: SELV @ 1A
1 x VFCO Fire Relay: SELV @ 1A
1 x Auxiliary Output: 24Vdc @ 250mA
InputsSounder Alarm Outputs: 4 x 150mA @ 24Vdc
Sounder CircuitSounder Activation Delay: 0 to 9 Minutes – In 1 Min Increments
Sounder End of Line Device: 10K Resistor
Mains Voltage230Vac +/- 10% @ 50/60Hz
System Voltage28Vdc Nominal (19 – 32V)
Charger Voltage27.6V @ 25°C (No Batteries Connected)
Total PSU Output5A
Battery Capacity2 x 12V 17Ah SLA (Max)
Battery Cut-off VoltageLess Than 20.5Vdc
Dimensions W x H x D485mm x 477.5mm x 125mm (19.09in x 18.80in x 4.92in)
Cable EntriesTop: 20 x 20mm Knockouts
Bottom: 6 x 20mm Knockouts
Mounting Points3
MaterialMild Steel
ColourRAL 7035
Operating ConditionsOperating Temperature: 0° to +50°C (32°F to 122°F)
Humidity: 0% to 95% RH, non-condensing
IP RatingIP30
Design EnvironmentIndoor Use Only

Downloads

Buy

The ProFyre C24 conventional fire alarm panel has been discontinued. Please contact us below for an alternative modular fire alarm panel.

ProFyre C24, 8 Zone Conventional Fire Alarm Panel

13-010
POA
Contact Us

ProFyre C24, 16 Zone Conventional Fire Alarm Panel

13-011
POA
Contact Us

ProFyre C24, 24 Zone Conventional Fire Alarm Panel

13-012
POA
Contact Us