Eurofyre Knowledge Base

Talentum UV/IR2 Flame Detector

Knowledge Base

Key Features

Talentum UV/IR2 Flame Detector
Talentum UV/IR2 Flame Detector
Talentum UV/IR2 Flame Detector
  • Combined ultraviolet and infrared sensing
  • Strong resistance to false alarms from non-flame sources
  • Works in dusty or variable lighting environments
  • Remote and automatic self-test functions
  • Flexible output and response options

Overview

The Talentum UV/IR2 Flame Detector combines ultraviolet and infrared sensing to detect open flames quickly and accurately. It responds to the unique light signature of flames, helping you spot fires with confidence while avoiding false alarms from hot surfaces or flickering lights. The detector works reliably in areas with dust, vapour or changing lighting conditions, making it suitable for demanding industrial environments.

The Talentum UV/IR2 can be used indoors or outdoors. It includes built-in self-test functions that let you check performance without physical access. The detector offers selectable output options and response settings so you can match it to your fire system and control needs.

This flame detector meets recognised standards and integrates with conventional fire alarm systems and process control panels. It offers dependable early warning of flame events in high-risk areas where fast fire detection matters.

Turntable

Talentum UVIR2 Flame Detector
Talentum UVIR2 Flame Detector
Talentum UVIR2 Flame Detector

Approvals

Tech Specs

Supply voltage14 to 30 V DC
Quiescent current8mA, RL2 energised
4mA, current loop, RL2 off
3mA, RL2 off
Alarm current28mA, RL1 & RL2 energised 
20mA, current loop, RL1 & 2 off 
9mA, RL1 energised
Power-up time 2 seconds max.
Self test voltage14 to 30 V DC
Relay outputsProgrammable operation including latching or non-latching
Relay maximum current0.75 A
Relay maximum voltage48 V DC
Relay maximum power30 W
Operating temperature-10°C to +55°C 
FM: -20°C to +60°C 
Storage temperature-20°C to +65°C
IP rating IP65
Range high (Class 1)*0.1 m² n-heptane at 25m
Range low (Class 3) 00.1 m² n-heptane at 12m
Field of view 90° min. Cone
Spectral response UV185 to 260nm
Spectral response IR1.0 to 2.7μm
Housing materialDie cast zinc alloy (ZA12)
Housing colour Blue RAL 240 50 35
Dimensions (W x D x H)108 x 79 x 142mm
Weight1.75 kg
Cable gland entries 2 x 20mm
Wiring1.0 to 4.0mm² (12 – 18 AWG)

Downloads

    Contact Eurofyre