Key Features

E2S A100 Alarm Horn Sounder
E2S A100 Alarm Horn Sounder
E2S A100 Alarm Horn Sounder
  • Compact, high-output sounder delivering up to 110dB(A) at 1m
  • 64 alarm tones with 4 remotely activated alarm stages
  • CPR compliant and tested to EN 54-3, with UL/cUL and ULC approval
  • SIL1 and SIL2 compliant to IEC 61508 as standard
  • IP66 rated, flame-retardant ABS enclosure with tropicalised electronics

Overview

The E2S A100 is a compact, high-output conventional alarm horn sounder from the AlertAlarm family, suitable for fire, security and process control signalling applications. It combines low current consumption with a sound output of up to 110dB(A) at 1m and an effective range of up to 38m at 1kHz. Sixty-four alarm tones are available, including UKOOA/PFEER compliant tones, with four remotely activated stages and on-board volume adjustment.

Multiple units synchronise automatically, whilst duplicate pluggable Class A cable terminations simplify wiring and maintenance. The A100 is housed in a robust UL94 V0 and 5VA flame-retardant ABS enclosure rated to IP66, with conformal coated electronics for use in humid or demanding environments. It is available in a wide-range 10–60V DC version and a 24–260V AC version, in red, grey or white, and is diode polarised for use on supervised circuits.

Turntable

E2S A100 Alarm Horn Sounder
E2S A100 Alarm Horn Sounder
E2S A100 Alarm Horn Sounder

Approvals

Tech Specs

Maximum Sound Output110 dB(A) ±3 dB at 1 m (101 dB(A) at 3 m)
Nominal Sound Output102 dB(A) ±3 dB at 1 m (93 dB(A) at 3 m)
Effective Range38 m at 1 kHz
Volume Control-12 dB(A) (tone dependent)
Number of Tones64 (UKOOA/PFEER compliant)
Alarm Stages4
Stage SwitchingNegative switching, common positive
Voltage (DC Version)10–60 V DC
Voltage (AC Version)24–260 V AC 50/60 Hz or 60–260 V DC
Current Consumption (DC Version)17 mA (12 V DC), 33.5 mA (24 V DC), 113 mA (48 V DC)
Current Consumption (AC Version)25 mA (115 V AC), 17 mA (230 V AC)
Inrush Current636 mA within 4.0 ms at 24 V DC
Safety Integrity LevelSIL1 and SIL2 Route 2H, IEC 61508 (2010) 
Enclosure MaterialHigh-impact UL94 V0 and 5VA flame-retardant ABS
Enclosure ColoursRed, grey, white
Cable Entries2 x M20 or ½” NPT clearance (single rear 20 mm entry on B back box)
Terminals0.5–2.5 mm² (20–14 AWG)
Ingress ProtectionIP66, Type 3R/13
Operating Temperature-40 °C to +66 °C
Storage Temperature-40 °C to +70 °C
Relative Humidity95% at 20 °C
Dimensions86.4 mm x 86.6 mm (S and M back boxes), 97.5 mm across mounting lugs
Weight0.26 kg (DC version), 0.37 kg (AC version) 
ApprovalsUL, cUL, ULC, UL EU (EN 54-3), CPR, MED, DNV, USCG, EAC, RMRS, CE, UKCA

Downloads

    Contact Eurofyre