Key Features
- Early warning of Lithium-ion battery failures
- Compatible with all Lithium-ion battery form factors and chemistries
- Reduction/removal of false positive signals
- Highly reliable output signal
- Calibration-free
Overview
This product has been discontinued and has been replaced by the Li-ion Tamer Controller, Gen 3. Please contact Eurofyre further information, spare parts, servicing and training.
Li-ion Tamer rack monitoring systems provide an early warning of battery failure. These detection systems are able to detect battery failure at the earliest possible time by monitoring for off-gassing events. Off-gassing occurs at the early stages of battery failure and is followed by thermal runaway which eventually leads to fire. By detecting the presence of off-gas within a battery rack, battery failures can be quickly located and dealt with before the battery catches fire and causes further damage.
Monitoring sensors are installed within the battery racks and reference sensors are installed outside of the battery rack to monitor the ambient environment. The Li-ion Tamer controller is installed in a separate location to the batteries and monitors the signals from both sets of sensors to provide fast and reliable detection of failure while mitigating nuisance alarms.
The controller has two types of communication protocols: digital outputs and Modbus serial communication. Both protocols report if a monitoring sensor has been activated. They can also report which monitor has been activated, allowing the user to quickly locate the rack that has reported the off-gas event.
Up to 12 monitor sensors and 3 reference sensors can be monitored by each Li-ion Tamer controller.
Turntable
Approvals
Li-ion Tamer controllers are ETL listed to UL61010 and CASA 22.2 No.61010 for products safety, are EN61326 certified for EU directive (2014/30/EU) and are RoHS 3 EU 2015/863 compliant.
Tech Specs
Dimensions (W x H x D) | 210mm x 63mm x 113mm |
Input power range | 8 – 28 VDC |
Max sensors per controller | 15 |
System outputs | Digital Outputs/Modbus |
Controller (no sensors) Power Consumption | 2.4 W (@ 24VDC)1.4 W (@ 12 VDC) |
Sensor Power Consumption | 275 mW (@ 5 VDC) |
Controller (fullypopulated, 15 sensors) Power Consumption | 6.6 W (@ 24 VDC)5.6 W (@ 12 VDC) |
Fuse Rating | 3.5A |
Baud rate | 9600 |
Parity | None |
Stop bit | One |
Hardware | RS232 3-wire (TX, RX, ground) |
Target lifetime | > 10 years |
Warranty | 1 year |
Target gases | Lithium ion battery off-gassingcompounds |
Min. detection threshold | < 1 ppm/sec |
Response time | 5 seconds |
Fault detection | Single cell failure |
Temperature | -10 to +60°C |
Humidity | 5 to 95% RH |
Max temperature change | 8.6oC/min |
Output Connector type | 2 x 10-pin Molex |
Signal type | Digital |
Signal level, normal HIGH, 8 – 28 VDC | HIGH, 8 – 28 VDC(Input voltage) 100mA max per channel |
Signal level, alarm | LOW, ~0 VDC |
Downloads
Buy
Eurofyre is an authorised distributor of Honeywell and has been a major technical wholesaler of Xtralis products since 2007. We offer expert advice and supply all aspects of Li-ion Tamer lithium ion detection systems including excellent before and after-sale support.
Contact us to receive competitive trade discounts or apply online for a credit account.
This product has been discontinued and has been replaced by the Li-ion Tamer Controller, Gen 3. Please contact Eurofyre further information, spare parts, servicing and training.