Key Features

  • Single or dual channel fire detection
  • Uses analogue addressable or conventional detectors (not supplied)
  • Multiple configuration options
  • Multiple detection strategies
  • Highest fan capacity in its class

Overview

ICAM IAS is a flexible aspirating smoke detector from Xtralis. The ICAM IAS is well suited for a range of applications. The ICAM IAS provides fast and reliable detection that can be integrated with any existing fire alarm control panel – helping to maintain aesthetics of a property, provide a tamper proof detection solution or simply replace traditional point detectors.

The ICAM IAS combines standard field-serviceable detectors with a stand alone air-sampling solution. ICAM IAS detectors actively draw air from the protected area, through sampling holes in a network of pipe, to its detection chamber. The sampled air is then analysed by conventional or analogue point detectors that are installed within the chamber.

The IAS is available with one inlet pipe (IAS-1) or two inlet pipes (IAS-2) and is compatible with photoelectric technology.

The ICAM IAS is a cost effective and simple to install and configure aspirating smoke detection solution. On top of this, in applications where an existing fire detection system is already in place, the ICAM IAS systems can be easily integrated with the existing fire alarm control panel.

Detection Strategies

ICAM IAS systems can be configured for single or dual addressable area detection, redundant detection, multi-criteria detection, coincident or double-knock detection and more.

Additional Features

  • IP65 enclosure
  • Up to 50m (328 ft) per sampling pipe
  • Microprocessor controlled
  • Integral display and programmer
  • Field serviceable air filter
  • Adjustable aspirator speed with airflow monitoring

Approvals

The ICAM IAS is fully approved by VdS for safe use and installation in any European Union country and bears the CE mark to show that it complies with all the applicable Directives including the CPR, EMC and the Low Voltage Directive (LVD).

  • EN54-20:2006 + AC:2008 – Fire detection and fire alarm systems – Control and indicating equipment.

Tech Specs

Detectors1 or 2 analogue addressable or conventional spot (point) detectors
A variety of detector technology types (photoelectric, ionization, heat, CO etc.)
Spot (point) detectors with universal screw mounting
Inlet Pipe SizeOuter Diameter: 25 mm (0.98 in.)
Inner Diameter: 21 mm (0.83 in.)
Sampling HolesEN54-20:
Class C (1 hole)
Sampling NetworkPipe Length: Up to 50 m (328 ft) per inlet
Pipe length may vary subject to specifications by local codes and standards, please refer to your regional IAS product guide for further detail
Supply Voltage24 VDC nominal (18 to 30 VDC)
Note, that spot (point) detectors are powered from the fire alarm field wiring
Operating Current300mA max (fan speed dependent)
Relay OutputsIAS-1: 1 fault relay
IAS-2: 2 fault relays
Flow Monitoring and ReportingHigh and Low adjustable Fan:
Control: 10 programmable speeds
Pressure: 250 Pa
Operating ConditionsTemperature: -10 to 60 °C (14 to 140 °F)
Humidity: 10 to 95% RH (non-condensing)
IP RatingIP65
FiltrationServiceable filter
External filter optional
Dimensions (W x H x D)259 mm x 184 mm x 166 mm (10.2 in. x 7.2 in. x 6.5 in.)