Key Features
- Improved false alarm immunity
- Tri-colour LED offering red, green and amber colours
- Rotary decade address switches
- Pure white colour to compliment modern buildings
- New base design to compliment the detector
Overview
System Sensor addressable fire detection systems use an advanced protocol to deliver greater control, configurability and device management to provide far greater flexibility than ever before.
System Sensor Addressable Optical Smoke Detectors have an entirely reimagined detection chamber design that delivers improved responsiveness, reduced sensitivity changes caused by settling dust and reduces false alarms caused by insects and other debris.
These optical smoke detectors use sophisticated processing circuitry that incorporates smoothing filters to help eliminate transient environmental noise conditions that can be the cause of unwanted alarms.
System Sensor Addressable Optical Smoke Detectors are managed by integrated software that runs sophisticated algorithms to further improve resilience to false alarms and improve detection speed.
The detector unit has two, integral, tri-colour LEDs that provide 360° local visual indication of the device status. The LEDs are programmable with static or blinking red, amber and green status indications available.
System Sensor detectors are environmentally friendly and meet the WEEE and RoHS legislative requirements, minimising end of life disposal costs, and are mechanically and electrically backwards compatible with existing Series 200 plus devices.
Turntable
Approvals
Tech Specs
Operating Voltage Range | 15 to 32Vdc |
Maximum Standby Current | 200μA at 24VDC (no communications) / 300μA at 24VDC (LED blink enabled, once every 5s) |
LED Current | red: 3.5mA at 24VdcGreen: 7.0mA @ 24VdcYellow: 10.5mA @ 24Vdc |
Remote Output Voltage | 22.5Vdc @ 24Vdc |
Remote Output Current | 10.8mA @ 24Vdc |
Additional loop resistance using the B501AP | typ 20mohm (max 30 mohm) |
Operating Voltage Range | 15 to 28.5Vdc |
Isolation Current Range | 15mA at 24VDC |
Maximum Continuous Current | 1A (Switch Closed) |
Temperature Range | 30°C to +80°C✝ |
Humidity | 10 to 93% relative Humidity (non-condensing) |
Height | 52mm installed in B501AP base |
Diameter | 102mm installed in B501AP base |
Weight | 97g (inc base) |
Max Wire Gauge for Terminals | 2.5mm2 |
Colour | White |
Material | PC/ABS |
† Do not install detectors in locations where normal ambient temperature exceeds 50°C
Downloads
- System Sensor Addressable Optical Smoke Detector Datasheet
- System Sensor Addressable Optical Smoke Detector Installation Manual
Buy
Eurofyre is an authorised distributor of Honeywell and we support the entire Morley IAS and System Sensor range of products. We offer expert advice and supply all aspects of fire detection systems including excellent before and after-sale support.