Key Features
- Compliant with EN54-22
- Connect up to four 16km cables
- Rapid detection and localisation
- Wide temperature range
- Sensor, relay and display in a single box
Overview
The DTSX1 employs Distributed Temperature Sensing (DTS), a type of linear heat detection whereby the fibre optic cable itself is the heat sensing element, capable of providing near-pinpoint locations and temperature accuracy across long distances.
Capable of detecting high heat over a wide area quickly and precisely, the controller incorporates all heat detection functions in a single box along with relays and display. Easily configurable, the alarm display and sounder can be programmed to your specific requirements, enabling rapid early warning of fire and identification of heat alarm conditions.
In addition to the DTSX1 Fiber Optic LHD Controller, all you need to create a LHD system is a LHD Fiber optic cable – up to four can be connected to the controller on separate channels giving a total range of up to 64km.
The DTSX1 controller excels at heat sensing over long distances and a wide temperature range of -25° to +70°C due to an innovative light scattering principle which not only allows differences in temperature to be accurately recorded, but also accurately located along the length of the cable.
The DTSX1 can accurately detect multiple hotspot locations simultaneously and sound the alarm at various presets to protect important assets before rising temperatures result in fire or require intervention.
Turntable
Approvals
DTSX1 fully complies with UK safety standards as well as EN54-22, the European fire safety standard governing linear fire detection systems and their components.
Tech Specs
Measurement distance range | 2, 4, 6, 8, 10, 16km |
Number of channels | 1, 2, 4 |
Spatial resolution | 1m or less (The length at which a 10% to 90% temperature change is detected at the near end of the fiber optic sensor cable when sampling a 16 km or less range at 0.5m intervals) |
Sampling resolution | Measuring temperature at 0.5m or 1m intervals |
Minimum temperature measurement time | 5 seconds |
Measurement mode | Single-ended, double-ended |
Number of zones configured | 1,000 (no overlapping) |
Optical output | E2000/APC 50/125μm GI |
LAN | 10BASE-T or 100BASE-TX Modbus/TCP |
Relay output | 8, 64 ports, max 35V/1A DC |
Relay input | 4 ports ON: 12 to 30V/5mA DCOFF: 3V/2mA DC |
Display | POWERSYSTEMOPERATINGALARM/PRE-ALARM/FAULT(Displayed for each channel) |
Switch | RESET: Alarm state resetACK: Alarm acknowledgement (Hold the alarm state) |
Power supply | Voltage 10 to 30V DC(Rated voltage: 12 to 24V DC) |
Power consumption | 30W (normally 15W at 23°C ambient temperature) |
Dimensions (W×H×D) | 500mm × 500mm × 250mm |
Weight | 28kg |
Mount type | Wall mount |
Downloads
DTSX1 Fiber Optic LHD Controller Datasheet
Buy