Search

Standalone Combustible Gas Detector

Search

Key Features

[
    {
        "id": "324",
        "cid": "310",
        "ext": "jpg",
        "priority": "1",
        "desc": "NULL"
    }
]
  • Loud 85dB Alarm
  • Power, Fault & Alarm Indicator
  • Two Phases Alarms
  • Test/Silence Function
  • Concentration LED Display
  • Mains/DC Power Selectable

Overview

The Standalone Combustible Gas Detector has been designed with the same dimensions as a standard 2 gang fitting, so it can be installed either surface mounted with it’s own backbox, or with a standard recessed box for semi-flush mounting.

There are two versions available. One calibrated for Natural gasand the other calibrated for LPG. Each unit can be powered either from 230V AC mains, or from a DC supply (9-28V DC).

The unit has a built in bar graph display to show the current gas level as a %LEL reading, and has a 2 stage relay output which operates at first alarm level (10%LEL) & second alarm level (25%LEL). There is also a 5V alarm output capable of supplying 200mA.

Power, fault & alarm indications are provided, as well as a control button for mute (press) and reset (Press & hold for 5 seconds).

Tech Specs

Part No

38-014 (Natural Gas)

38-015 (LPG)

Supply Voltage

230V @ 50/60Hz AC or 9 -28V DC

Quiescent Current

140mA

Start-up Current

220mA

Alarm Current

500mA (excluding Alarm output)

Buzzer Output

85dB@ 3m

Operating Temperature

0ºC to 50ºC

Max. Humidity

95% RH N/C

Response Time

Less than 30 seconds

Senstivity

38-014: 4400ppm

38-015: 1700ppm

Size (W x H x D)

150mm x 90mm x 70mm

Weight

1 kg

Part Codes

38-014Standalone Combustible Gas Detector, Natural Gas
38-015Standalone Combustible Gas Detector, LPG

Downloads