Key Features
- EN54-20 approved
- Dual pipe air-sampling
- Single zone
- Area coverage up to 2000m2
- 0.001% to 20% obscuration/m
Overview
The Xtralis ICAM IFT-P Aspirating Smoke Detector is a very early warning smoke detector that can reliably detect fire during its early stages. ICAM IFT-P detectors have a sensitivity range from 0.001% to 20% obscuration/m (0.0003% to 6.10% obscuration/ft) and can detect low to high concentrations of smoke over an area of up to 2000 m2 (21 500 ft2).
Xtralis ICAM IFT-P detectors can be configured to suit an assortment of different environments and can provide reliable and accurate smoke detection for heavy industrial applications such as factories, chemical plants, mining facilities and warehouses as well as telecommunications and IT facilities.
How It Works
IFT-P detectors use powerful aspirators to draw air through sampling holes in an aspirating pipe network. The air is then filtered before being analysed in the detectors laser detection chamber.
The detectors aspirator is a 2000 Pa high volume and high-pressure fan. This provides superior detection times over long pipe lengths and reliable detection in high airflow environments. The airflow of each pipe is monitored by a dual element thermal sensing system. Airflow faults are indicated on the detector’s display and sent to monitoring equipment.
Four individually programmable alarm states (Alert, Action, Fire 1 and Fire 2) are shown using the detectors LED display, along with an OK/Fault indication. Dedicated output relays also provide interfaces for each alarm state and device fault.
Programming and Configuration
IFT-P detectors can be configured using Xtralis’ Configuration and Fire System Management software packages, Xtralis VSC and Xtralis VSM4, via RS232, RS485 and TCP/IP communication interfaces. The RS485 interface also allows connections to remote displays, and the TCP/IP Ethernet Interface can provide access to an email messaging service.
The IFT-P detector supports a maximum of three optional modules, which provide the detector with additional programmable output relay interfaces, and 4 to 20 mA analogue outputs.
Approvals
The ICAM IFT-P is fully approved by VdS and LPCB for safe use and installation in any European Union country and bears the CE mark to show that it complies with all the applicable Directives including the CPR, EMC and the Low Voltage Directive (LVD).
EN54-20:2006 + AC:2008 – Fire detection and fire alarm systems – Control and indicating equipment.
Tech Specs
Supply Voltage | Nominal 24Vdc |
Supply Current | 500mA (min) to 1.2A (max) |
Capacitive Loading | Nominal 5,000 uF |
Aspirator | 2000Pa Centrifugal air pump |
Dimensions (W x H x D) | 254mm x 180mm x 165mm (10.0in. x 7.1in. x 6.5in) |
Operating Conditions | Ambient: 0 to 39°C (32 to 103°F) UL Listed Detector Installed Ambient conditions 0°C to 38°C (32°F to 100°F) Tested to: -10 to 55°C (14 to 131°F) Sampled Air: -20 to 60 °C (-4 to 140°F) Humidity: 10 to 95% RH (non-condensing) |
Sampling Pipe Size | Outer Diameter: 25 mm, or; 1.05 in (3/4” pipe) with adaptor |
Sampling Holes | EN54-20: Class A (12 holes / 0.04% obs/m) Class B (36 holes / 0.04% obs/m) Class C (36 holes / 0.1% obs/m) |
Sampling Network | Zones: 1 Fire detection zone Pipe Length: 2 x 100m (2 x 328ft) |
Alarm Sensitivity Range | 0.001% to 20% obs/m (0.0003% to 6.10% obs/ft) |
Alarm Settings | Alarm levels: Alert, Action, Fire 1 and Fire 2 Alarm delays: 0 to 60 seconds Individually programmable for each level |
IP Rating | IP65 |
Filtration | Field exchangeable dual stage filter |
Flow Monitoring | Twin thermal element |
Relay Outputs | 4 alarm relays, 1 fault relay, 1 Amp changeover Rating 1A @ 30Vdc, NO/NC |
Communication | RS232, RS485 Modbus Ethernet TCP/IP |
Event Log | Up to 20,000 events stored |
Downloads
Buy
Eurofyre is an authorised distributor of Honeywell and has been a major technical wholesaler of Xtralis products since 2007. We offer expert advice and supply all aspects of VESDA, FAAST and ICAM aspirating smoke detection systems including pipework calculations, demonstration/training and excellent after-sale support.