Key Features
- Anti-fog lens and reflector
- EN54-12:2015 approved
- Range of up to 160 metres
- Self-aligning
- Automatic drift compensation
Overview
The Fire Beam Xtra is an advanced beam detector. The Fire Beam Xtra self-aligns itself to the centre of the reflector when commissioning and will automatically keep alignment when building movement occurs. Its enhanced optics can cover distances of up to 160 metres and, thanks to completely new linear stepper motors, can be commissioned five times faster than the original Fire Beam.
Automatic alignment takes just over three minutes to complete out of the box and routine realignment can be carried out in just over one minute.
Auto alignment can be turned off for environments that may be subject to occasional contamination (such as theatres using fake smoke). This means that the detector won’t try to re-align itself should the reflector become obscured. An auto-align time delay is also available for environments that might suffer occasional short-term obscuration. By adding a delay, the beam will not check if the received signal drops for a predetermined time.
The Fire Beam Xtra supports seven different languages: English, German, Spanish, French, Italian, Dutch and Czech.
In environments where warm air meets a cold surface, condensation can occur on the Fire Beam’s lens and reflector. This makes it difficult for the detector to determine whether or not smoke is present.
Fire Beam Xtra Beam Detector, Anti-fog provides all the benefits of Fire Beam Xtra, but with an anti fog lens and reflector that feature a special nano coating that prevents condensation from forming.
The Kit



The Fire Beam Xtra Kit comes complete with the head unit with anti-fog lens, a low level controller, a single anti-fog reflector, a user manual and a 3mm allen key. This will enable you to cover distances up to 70 metres. To cover distances over 70 metres a Range Kit can be added to extend the coverage up to 160 metres.
Approvals


Tech Specs
Supply Voltage | 10.2 to 30 VDC |
Supply Current | 3.5mA (constant current) in all operational states |
Constant Current | 17mA (constant current) in fast commissioning |
Temperature | -10°C to +55°C |
Humidity | 10 to 95% RH Non-condensing |
Protection Index | IP65 when suitably mounted and terminated |
Dimensions (W x H x D) | Beam Head: 155mm x 180mm x 137mm, 1.10kgController: 120mm x 185mm x 62mm, 0.55kgMid Range Kit: 293mm x 293mm x 5mm, 0.8kgLong Range Kit: 394mm x 394mm x 5mm, 1.8kgUnistrut Adaptor (mounts the Beam Head onto Unistrut): 270mm x 250mm x 5mm, 0.6Kg |
Optical Wavelength | 870 nm |
Maximum Angular Alignment | ±5° |
Maximum Angular Misalignment | Beam Head ±0.75° / Reflector ±2° |
Fire Beam Xtra Protection Range | As standard up to 70 metres |
Mid Range Kit Protection Range | 70 to 140 metres |
Long Range Kit Protection Range | 140 to 160 metres |
Alarm Sensitivity Levels | 25% (1.25dB) to 50% (3dB) in 1% (0.05dB) increments (default 35% (1.87dB)) |
Alarm Condition: | Obscuration drops to below pre-defined sensitivity level.Time to Alarm Condition adjustable between 2 to 30 seconds in 1 second increments (default 10 seconds) |
Alarm Indication: | Controller Status – FIREController Red Flashing LEDHead Red Flashing LEDAlarm Relay ChangeOver (CO) ContactRating 2A @ 30 VDC |
Test / Reset Features: | Beam test function by controllerAlarm latching / auto-reset selectable (default auto-reset)Alarm reset in latching mode by controller reset function, removing power for >5 seconds, apply 12 to 24 VDC to reset connections in Beam Head. |
Fault Sensitivity Level: | 90% |
Fault Condition: | Obscuration drops to below the fault sensitivity level within 1 secondPower Down or Supply Voltage < 9 VDCCommissioning modes, Pre-Alignment and Auto-AlignmentBeam turned off during Beam MaintenanceTime to Fault Condition adjustable, 2 to 60 seconds in 1 second increments (default 10 seconds) |
Fault Indication: | Controller Status – FAULTController Yellow Flashing LED 1 SecondHead Yellow Flashing LED 1 SecondFault Relay ChangeOver (CO) Contact Rating 2A @ 30 VDC |
Normal Condition: | Obscuration level is above the Alarm sensitivity levelController Status – NORMALController Green Flashing LEDProgrammable on/offHead Green Flashing LEDProgrammable on/off |
Auto-Align / Beam Contamination Compensation: | Auto-align during normal operation if obscuration drops below 90% for the duration of the align time set (doesn’t affect normal operating mode)Beam Contamination Compensation 4 hour monitoring. Compensation data available at the controller |