Key Features
- Data logging
- Three alarm stages + Relays
- 4~20mA analogue output
- Internal or remote sensor option
- Aspirated option
Overview
A fixed single point alarm unit that meets the requirements for economic and reliable monitoring of gas levels in a wide range of environments from commercial premises through to heavy industrial applications that may require hazardous area sensing.
The 101 may be utilised as a standalone unit or as an addressable sensor forming part of the Combi CANbus addressable network system and therefore offering the features of our most advanced system. Typical monitor locations are:
Public buildings |
Boiler plant rooms |
Swimming pools |
Water treatment works |
H&V control systems |
Manufacturing and process plants |
Tech Specs
Measuring Range | Combustible Gas – LEL, % Vol, ppm Toxic Gas – ppm Oxygen – % vol – Depletion or Enrichment Any 4~20mA source input signal |
Indicators | Two line alpha numeric back lit display Power – Green LED. Alarms 1, 2, 3 – Red LEDs Fault – Amber LED Alarms inhibit – Amber LED |
Audible Alarm | 1, 2, 3 and Fault Alarms – mutable 85dB @ 10cm |
Power Supply | 24v nominal 18v to 30vDC Option – 230/115v AC 50/60 Hz The two voltages may be utilised simultaneously – standby supply |
Power Consumption | 4 watts – full alarm |
Outputs | 1, 2, 3 and fault alarm relays – SPCO normally de-energised – energised option, latched or unlatched All contacts rated 3A – 230v AC Selectable inhibit active indicator or re-settable sounder output – O/C 100mA – 24DC 4-20mA, Sink/Source CANbus |
Alarm Settings | Digital setting (fully adjustable between zero and full scale) Delay to alarm |
Sensor Inputs | Bridge type 3 wire detector mv (Catalytic) 4-20mA (electrochemical / infrared / catalytic / PID / semiconductor) |
Sensor Cable | 3 core 1.5mm2 screened 1.5km |
Miscellaneous | Operating temperature -15 to +50˚C Storage temperature -5 to 55˚C Alarm relay inhibit during calibration Sounder Inhibit System function test |
Dimensions (L x H x D) | 145mm x 145mm x 65mm 24vDC version 145mm x 145mm x 100mm AC version |
Weight | 0.8kg |
Ingress Protection | IP64 |
Gases
Gas list available on request.