Key Features
- UL 521 approved
- Cable based sensing allows detection at the point of risk
- Low installation, maintenance and repair costs
- Reliable solution for hazardous areas
- Low material cost
Overview
Messenger wire is used to install linear heat detection cable in areas which may be difficult to access, have large spans to cover or where fixing the cable at the normal recommended spacing (up to 1.5m/5ft intervals) would be too difficult or time consuming.
FyreLine Digital is suitable for most environments. FyreLine Digital Linear Heat Sensing Cable has a PVC outer coating as standard and is suitable for a variety of applications. It is used to detect excess heat at any point along its length. Once the cable’s rated temperature is reached, a signal is sent to the fire alarm control panel.
FyreLine Messenger Wire is available as an optional addition to FyreLine Digital Linear Heat Detection Cables to ensure the cable is supported correctly.
Cable Construction
FyreLine Digital Linear Heat Detection Cable is made up of two twisted cores that are separated by an advanced temperature sensitive polymer. When the polymer reaches its rated temperature it softens and allows the cores to come into contact, this event alerts the fire alarm panel to take appropriate action. This is an irreversible process and once the cable has activated, the section which has triggered must be cut out and replaced.
FyreLine Digital Linear Heat Detection Cable with Messenger Wire comes with the messenger wire already spiralled around the cable to make the detector cable self-supporting.
Approvals
FyreLine digital linear heat detection cables are fully approved by the Underwriters Laboratories (UL) and bear the CE mark to show that they comply with all the applicable Directives including the CPR, EMC and the Low Voltage Directive (LVD).
UL 521 – Heat detectors for fire protective signalling systems.
Tech Specs
Construction | Overall insulated, twisted pair of tri-metallic cores |
Insulation | 1kV tested protective outer coat |
Approvals | CE Marked, UL Listed |
Maximum Zone Length | 3,000m (10,000ft) |
Overall Diameter | 3.60mm ± 0.12mm (0.142” ± 0.005”) |
Minimum bend radius | 50mm (2”) |
Max Voltage Rating | 30Vac, 42Vdc |
Resistance | ~100Ω/km (29Ω/kft) per leg |
Velocity of Propagation | ~55% |
Capacitance | 88 – 150 pF/m (26 – 45 pF/ft) |
Inductance | 540 – 1050 nH/m (165 – 320 nH/ft) |
Downloads
- FyreLine Digital PVC LHD Cable with Messenger Wire Datasheet
- FyreLine Digital Technical Sales Brochure
- FyreLine Digital Linear Heat System Guide
- FyreLine Digital Approval Certificate (UL)
Buy
Contact us for trade discount and credit opportunities.