Key Features

  • Fully compliant to BS8300:2009
  • Standalone system controller for one zone
  • Light grey double gang plate
  • LED indication and braille enhanced accept button
  • Combined controller and PSU

Overview

Emergency Voice Communication (EVC) systems empower individuals with disabilities or mobility challenges to request assistance during emergencies.

Building owners have the responsibility of ensuring the safety of everyone who uses their property and building regulations mandate the installation of suitable emergency assistance alarm systems in specific areas, including disabled toilets.

Crisis Assist Emergency Assistance Systems offer a comprehensive solution to provide aid and support during emergency situations. Incorporating features and components to facilitate quick response and assistance to individuals in need, Crisis Assist enhances safety and security by providing timely assistance and support during emergencies, helping to minimise risks and mitigate the impact of crisis situations.

Crisis Assist Disabled Toilet Alarm Controller, 1 Line

The Crisis Assist Disabled Toilet Alarm Controller, with one line (zone), provides clear audio and visual feedback, housed in a sleek light grey finish that seamlessly integrates into any environment.

Designed to enable the continual monitoring of a single zone, the Crisis Assist disabled toilet alarm controller should be located in a permanently staffed area where assistance calls can be received and actioned as quickly as possible. 

During an alert, the controller features audio and visual indication of an alarm. An integrated buzzer sounds and the unique blue “halo” indicator around the Accept button flashes for visual indication of a call. Once the staff member presses the braille-enhanced Accept button, the sounder is muted and the LED halo turns solid until the alarm is cancelled or reset at the origin of the alarm.

Crisis Assist Disabled Toilet Alarm Controller, 1 Line

Typical Wiring Diagrams

The Crisis Assist Disabled Toilet Alarm Controller can be used to create a standalone EVC system when used with other Crisis Assist products, and is also available as part of a kit. An alternative four line controller to allow the effective monitoring of up to four zones is also available.

Standard two-core cable suffices for all wiring needs, including speaker, bell wire, and Twin & Earth, ensuring ease of installation. What sets Crisis Assist apart is the absence of a fixed wiring order for devices, granting designers complete freedom in determining installation routes where the units can be wired in any order, ending with a 10K End Of Line resistor.

The unit boasts high-quality two-part terminals, suitable for 2.5mm CSA cable, ensuring durability and reliability. Additionally, an optional NiMH rechargeable backup battery offers extended functionality, providing peace of mind in case of power outages.

Standalone

Approvals

Tech Specs

StandardsBS8300:2009
Building Regulations Approved Document M: 2010
Supply230VAC +- 10%
Battery BackupOptional 600mA NIMH Rechargeable Battery
CablingTwo core 0.4mm to 2.5mm CSA (max return resistance 10 Ohms)
Relay Output30V 1A NO Volt Free
Alarm Output50-80dBA
Dimensions (W x H)146mm x 86mm
Back Box Information35mm deep double gang flush or round corned metal surface box