Key Features

  • Up to 4 SLC modules
  • 4.3” colour touchscreen display
  • Capacity for up to 6 intelligent modules
  • Full system redundancy
  • Connection to TCP/IP module

Overview

The Velocity MMP/6 fire alarm panel is a powerful and sophisticated analogue addressable fire alarm control panel that can be expanded with an assortment of modular components. This makes the control panel extremely versatile and suitable for use in a variety of applications.

On the front of the Velocity MMP/6 fire alarm control panel is a 4.3 inch colour, touchscreen display that provides a clear, clutter-free and intuitive interface to enable easy operation with minimal training.

This versatile fire alarm control panel supports complex cause and effect programming and a variety of user controllable functions, all accessible from the integrated display or via the Velocity Connect PC software, which makes it suitable for a wide range of projects from multi-site commercial developments to industrial applications.

The Velocity MMP/6 control panel uses soft addressing via the VDOT-AD2 handheld programming tool to reduce installation time and minimise the risk of error that is typical of hard addressed devices.

These modular, multiloop fire alarm control panels can operate as standalone panels or as part of a peer-to-peer networked system of up to 64 panels. Sophisticated programming options allow control over whether messages from specific panels remain local or are transmitted around the network.

Velocity control panels support up to 254 devices per signalling line circuit (SLC) and have 254 programmable zones.

Panel Modules

Velocity MMP/6 fire alarm panels can be customised with a variety of modular components to make it suitable for almost any application. Modules currently available include:

  • VL-SLC – Signalling Line Circuit Module

    The VL-SLC module provides power for and handles communications with analogue addressable devices.

    Read More
  • VL-ZMA – Zone Monitor Module, Class A

    The VL-ZMA is a three zone module. This module has three class A zone monitors which can be used for conventional detectors that are not available in addressable form.

    Read More
  • VL-ZMB – Zone Monitor Module, Class B

    This is a six zone class B module. It has six class B zone monitors which can be used to monitor conventional devices and/or for special detectors that are not available in an addressable option.

    Read More
  • VL-NCA – Notification Appliance Circuit Module, Class A

    This module provides power for, and handles communications to, non-addressable notification appliances. The VL-NCA has one notification appliance circuit that can be wired in class A configuration.

    Read More
  • VL-NCB – Notification Appliance Circuit Module, Class B

    This module also provides power for, and handles communications to, non-addressable notification appliances but has two notification appliance circuits that can be wired in class B configuration.

    Read More
  • VL-MIM – Multi Input Module, Class B

    The VL-MIM has six class B inputs that are commonly used to monitor and raise alarms from any ancillary equipment such as sprinkler flow switches, aspiration detectors, secondary fire alarm control panels, beam detectors, external power supplies and more.

    Read More
  • VL-MRM – Relay Module, Form C

    The VL-MRM relay module has three form C relays which are typically used to control lift operation, fire pumps or ventilation fans in the event of a fire.

    Read More
  • VL-NWM – Network Module

    The Velocity VL-NWM network module accommodates up to 64 nodes. It is used to monitor, indicate and control the functions of a fire alarm installation and allows signals to be distributed around large sites.

    Read More
  • VL-MBM – Modbus Module

    The VL-MBM modbus module is used to link the Velocity fire alarm panel to a building management system (BMS) to control ventilation, lighting, power systems, fire systems and security systems in the event of a fire.

    Read More
  • VL-232 – RS232 (Printer) Module

    The VL-232 module gives a Velocity panel the ability to interface to RS232 serial equipment and devices. This is most commonly used to connect the Velocity MMP to an RS232 panel printer or a desktop printer for real time event log printing.

    Read More
  • VL-LAN – TCP/IP Module

    The VL-LAN TCP/IP module enables the fire alarm panel to be remotely monitored via the Zeta Smart Remote mobile application.

    Read More

Additional Features

  • Positive alarm sequence
  • Automatic drift compensation
  • Alarm verification
  • Mains trouble output delay programmable from 0 to 240 minutes
  • NAC special application 24V mode
  • 240W power supply

Approvals

All components in the Velocity range are UL certified and comply with the requirements of Underwriters Laboratories (UL) 864 Control Units and Accessories for Fire Alarm Systems 10th Edition.

Tech Specs

ProtocolVelocity
Max Module Capacity6
Zones254 Zones
Maximum Event Log8032 Events
Software ProgrammingTouchscreen LCD or Velocity Connect PC Software
Display4.3” Resistive LCD Touchscreen480 x 272 Pixel Resolution
LED Indicators1 Red (1 x Alarm)
1 Green (Power)
10 Yellow (1 x Supervisory, 1 x Trouble, 1 x Alarm Silenced, 1 x Controls Active, 1 x NAC Active, 1 x General Disablement, 1 x General Test, 1 x NAC Trouble/Disablement, 1 x NAC Delay, 1 x CPU Trouble)
Button ControlsSilence Alarm, Ack, Scroll, Reset, Drill
Outputs1 x Alarm Relay: 125V AC @ 0.5A / 30V DC @ 1A
1 x Trouble Relay: 125V AC @ 0.5A / 30V DC @ 1A
NetworkMaximum Network Size: 64 Nodes
Maximum Distance Between Nodes: 1KM
Mains AC Supply Voltage240/120V AC
Mains AC Supply Frequency50/60Hz
Power Supply DC Rating 30V DC 10A
Battery Voltage24Vdc
Battery Charge Current1.1A (Max)
Battery Capacity (Supervised)2 x 12Ah, 12 VDC Sealed Lead Acid (Max)
Dimensions  (W x H x D)385mm x 535mm x 150mm
Weight9kg
Cable Entries34
Operating Temperature0°C (32°F) to 49°C (120°F)
Relative Humidity93% Non-Condensing

Downloads

Buy

Velocity VL-MMP6 Fire Alarm Panel

Velocity MMP/6 Fire Alarm Panel

VL-MMP/6
POA
Contact Us