Key Features

  • BS8300 acknowledge feature
  • Designed and manufactured in the UK
  • High volume sounder
  • Flush or surface mount
  • Blue halo and Braille enhanced cancel button

Overview

All Crisis Emergency Voice Communication Systems (EVCS) are designed to comply fully with the requirements of BS5839-9:2011 for use as a disabled refuge system (DRS) with integrated Emergency Assist Alarm System.

The Crisis Assist Call Cancel Plate is used to cancel the alarm; the cancel plate should be mounted 1 metre from the floor and the level with the front of the toilet. The cancel plate is supplied as a single gang brushed stainless steel plate as standard with a blue ‘halo’ indicator for the visual alarm and a buzzer for the audible alarm. For simplicity all wiring is a standard two core cable, the wiring order of the plates is not fixed and therefore can be wired in any order to give total flexibility in the installation routes.

Tech Specs

StandardsCompliant with:
BS5839-9:2011, BS8300
EMC: EN55103-1:2009 and EN55103-2:2009
LVD: EN60950-1:2006
CablingCable Type: 1 x 2-core 1.0mm PVC or Fire Rated (sharing
a line with a Type B Refuge Outstation)
Maximum Distance: 500
Weight0.2kg (0.440Ibs)
Dimensions (W x H x D)86mm x 86mm x 22mm

Downloads

Buy

Crisis Assist Call Cancel Plate

36-403
POA
Contact Us