Key Features
- Provides two interfaces to NC/NO contact devices
- Address settable from 001 to 254 by a dedicated programmer
- Loop powered and low standby current (3mA)
- Single loop address
- Supports Class A and Class B wiring
Overview
The Velocity Addressable Dual Input Module is intended for use with addressable two wire systems. The Velocity Addressable Dual Input Module monitors and transmits the status (normal, open, short or active) of devices equipped with NC/NO dry contacts such as pull stations, water flow switches and security catches to a control panel. The initiating device circuit (IDC) can be wired as Class A (Style D & E) or Class B (Style B & C).
It has a built-in short-circuit isolator (SCI) to prevent loop failure in the event of a short on the loop.
The Velocity Addressable Dual Input Module is loop powered and can be mounted directly onto a 4-inch electrical box. It has three coloured LEDs to indicate the status of the input, polling and SCI.
Approvals
All components in the Velocity range are UL certified and comply with the requirements of Underwriters Laboratories (UL) 864 Control Units and Accessories for Fire Alarm Systems 10th Edition.
Tech Specs
SLC Applied Voltage | Rated Range 20 to 38 VDC |
SLC Current Consumption | Standby 3.0mA Activated 16.9 mA (max) |
SLC Line Impedance | Up to 50Ω |
Number of IDC (Initiating Device Circuit) | 1 x Class A or 2 x Class B |
IDC Circuit Rating | 15 V DC, 2.2 kΩ, 6.8mA (max) |
IDC Line Impedance | Up to 50Ω |
EOL Device | RE-10 k (10 kΩ, 1/4 W) (included) 2.2 kΩ resistance required for each dry contact switch in subtype setting 7, 8, 9 and 10 |
SCI on Resistance | 0.2 ohms (max) |
SCI Fault Detection Threshold | 10V (min) |
SCI Isolation Current | 22mA (max) |
Visual Indicator (Status LED) | Polling LED (GREEN) Input LED (RED) SCI LED (YELLOW) |
Ambient Installation Temperature | 0°C to 49°C (32°F to 120°F) |
Storage Temperature | -20°C to 60°C (-4°F to 140°F) |
Max Relative Humidity | Up to 93% RH, non-condensing |
Environment | Indoor dry use only |
Max Quantity Per Loop | 127 Units |
Terminal | Screw AWG 12 to 22 |
Address Setting | VDOT-AD2 Address Programmer |
Dimensions (W x H x D) | 124mm x 124mm x 34.5mm |
Weight | Approximately 154g |
Standard | UL864 |