Search

Velocity Class B Multi Input Module

Search

Key Features

  • Designed to meet UL864 10th Edition requirements
  • 6 x Class B input circuits
  • Each zone is monitored for open and short circuit
  • Quick and easy to install
  • Extensive front unit status indications

Overview

The Class B Multi Input Module is a six input module that is designed to be DIN mounted inside of a Velocity control panel. It is connected to the Velocity MMP control panel via an RJ45 connection that also provides power to the module.

The VL-MIM module has six class B inputs that are commonly used to monitor and raise alarms from ancillary equipment such as aspirating smoke detectors, sprinkler flow switches, secondary fire control panels, beam detectors and external power supplies.

The Class B Multi Input Module monitors and transmits the status (normal, open, short, or alarm) of inputs to the fire alarm control panel and each input can be programmed to give either a supervisory or alarm signal when active.

The VL-MIM module also has status indicators on the front to show that the module is  communicating with the motherboard, when the input is in an alarm/supervisory condition and when the input is in a trouble condition.

Approvals

All components in the Velocity range are UL certified and comply with the requirements of Underwriters Laboratories (UL) 864 Control Units and Accessories for Fire Alarm Systems 10th Edition.

Tech Specs

Design StandardUL864 10th Edition
ApprovalUL Laboratories
Wiring Class6 x Class B (Power Limited & Supervised)
Circuit Voltage24V DC Nominal (16V – 24.5V with EOL fitted)
Input Max Line Impedance10Ω
End of Line Resistor4K7Ω
Triggering Resistor1KΩ
Operating Temperature0°C (32°F) to 49°C (120°F)
Max Humidity95% Non-Condensing
Size (W x H x D)97mm x 103mm x 46mm
Weight0.2kg
Recommended Cable Sizes22 AWG to 18 AWG (0.3mm2 to 0.8mm2 )

Downloads

Buy