Search

Velocity Class A Zone Monitor Module

Search

Key Features

  • Designed to meet UL864 10th Edition requirements
  • 3 x Class A initiating device circuits
  • Each zone is monitored for open & short circuit
  • Extensive front unit status indications
  • Each zone input can be configured as either Alarm or Supervisory

Overview

The VL-ZMA is a three-zone monitor module that is designed to be DIN mounted inside of a Velocity control panel. It has three class A zone monitors which can be used for conventional devices and/or specialist detectors that are not commonly available in addressable form such as UV detectors, aspirating smoke detectors and beam detectors.

The VL-ZMA monitors the status (normal, open, short, or alarm) of zones and transmits it to the control panel and each zone input can be programmed to give either a supervisory or alarm signal when active.

VL-ZMA monitor modules are connected to the Velocity control panel via an RJ45 connection which also provides power to the unit.

Approvals

All components in the Velocity range are UL certified and comply with the requirements of Underwriters Laboratories (UL) 864 Control Units and Accessories for Fire Alarm Systems 10th Edition.

Tech Specs

Design StandardUL864 10th Edition
ApprovalUL Laboratories
Wiring Class3 x Class A [Power Limited & Supervised]
Circuit Voltage29V DC Nominal (19.5 – 30V)
Zone Max Current (under S/C conditions)56mA
Zone Max Line Impedance20Ω total (10Ω per core)
End of Line ResistorN/A
TriggeringResistor 1KΩ
Operating Temperature0°C (32°F) to 49°C (120°F)
Max Humidity93% Non-Condensing
Dimensions (W x H x D)97mm x 103mm x 46mm
Weight0.20kg
Recommended Cable Sizes22 AWG to 14 AWG (0.3mm2 to 2.5mm2)
Compatible DevicesVL-RS-01 (UL38 Listed)
Maximum Detectors Per Zone20

Downloads

Buy