Key Features
- High Sound Output
- Low Current Consumption
- 22 Tones (User Selectable)
- Semi-flush or Surface Fixing
- Housed in UL V0 Flame Retardant ABS
Overview
The Xtratone is an addressable loop powered wall sounder controlled by the fire alarm panel. It is designed to be low current and provides a range of tones with a maximum output of up to 102dB(A) (±2dB). Details of the tones range can be found in the table below.
A combined Sounder/LED Indicator version is also available.
Each device is supplied with a back box having four 20mm knock-outs for surface mounting purposes. The device is compact enough to be mounted directly on to a single European back box for semi-flush mounting. The Xtratone has an ingress protection rating of IP21C (with back box) for internal use only.
Mounting Options
The Xtratone has been designed to accommodate various indoor applications. A single version that can be mounted surface or semi-flush.
ProFyre Compatible Conventional Panels
The conventional Xtratone sounder has been designed to complement the ProFyre C8 and C24 conventional control panels.
Approvals
The ProFyre Conventional Xtratone Sounder is fully approved by LPCB for safe use and installation in any European Union country and bears the CE mark to show that it complies with all the applicable Directives including the CPR, EMC and the Low Voltage Directive (LVD).
- EN54-3:2001 + A1:2002 + A2:2006
Sounders
Alarm Tones
BS Fire (Default) | Pattern: Alternating Frequency: 800 & 970 Tone: 1Hz (500ms – 500ms) dB(A): 102 (±2dB) |
BS Fire | Pattern: Alternating Frequency: 800 & 970 Tone: 2Hz (250ms – 250ms) dB(A): 101 (±2dB) |
BS Fire | Pattern: Sweep Frequency: 800 & 970 Tone: 1Hz (1 Per Second) dB(A): 95 (±2dB) |
BS Fire | Pattern: Sweep Frequency: 800 & 970 Tone: 7Hz (7 Per Second) dB(A): 96 (±2dB) |
BS Fire | Pattern: Sweep Frequency: 800 & 970 Tone: 50Hz (50 Per Second) dB(A): 96 (±2dB) |
BS Fire | Pattern: Alternating Frequency: 510 & 610 Tone: 1Hz (500ms – 500ms) dB(A): 102 (±2dB) |
German Fire (NIN 33 404) | Pattern: Sweep (DIN) Frequency: 1200 to 500 Tone: 1Hz dB(A): 102 (±2dB) |
French Fire (NFS 32-001) | Pattern: Alternating Frequency: 554 & 440 Tone: 100ms – 400ms dB(A): 102 (±2dB) |
Dutch Fire (NEN 2575) | Pattern: Slow Whoop Frequency: 500 & 1200 Tone: 3.5s Sweep, 0.5s Silence, then repeat dB(A): 102 (±2dB) |
PFEER Toxic Gas | Pattern: Continuous Frequency: 970 Tone: Steady dB(A): 102 (±2dB) |
PFEER Alert | Pattern: Intermittent Frequency: 970 Tone: 0.5 Hz (1s On / 1s Off) dB(A): 102 (±2dB) |
Tech Specs
Operating Voltage | 17 to 28Vdc |
Quiescent Current | 0.65mA |
Alarm Current | 4.5mA |
Sound Output | See Alarm Tones Table |
Operating Conditions | Tested to: -10°C to +55°C (14°F to 131°F) Maximum Continuous Temperature: 0°C (32°F) Humidity: 0% to 95% RH, non-condensing |
IP Rating | IP21C |
Design Environment | Indoor Use Only |
Mounting | Semi Flush or Surface |
Weight | 0.20kg (0.44Ibs) |
Colour | Red or White |