Key Features
- Backward compatible with existing VESDA installations
- Multi stage filtration and optical protection
- Wide sensitivity range
- Smart on-board filter
- Autolearn smoke and flow
Overview
Introduction
VESDA-E VEP Aspirating Smoke Detectors are highly sensitive aspirating smoke detectors that provide increased reliability and advanced features. They provide a very early warning of fire and superior nuisance alarm rejection for a wide variety of applications.
Built on Flair Detection Technology, VESDA-E VEP Aspirating Smoke Detectors achieve consistent performance over their lifetime via absolute calibration. These detectors offer a range of revolutionary features that provide user value.
The VEP range offers absolute calibration, multi-stage filtration and optical protection with clean air barriers to provide continual detection performance.
A smart onboard filter retains a dust count and remaining filter life to allow maintenance to be scheduled in advance.
VESDA-E VEP detectors offer four alarm levels, a wide sensitivity range and use flow fault thresholds for each port to support changeable airflow conditions. They can deliver Class A, B or C aspirating smoke detection and are available in single or four pipe variations making this range of detectors suitable for a host of applications.
Area Coverage
Single pipe VESDA-E VEP detectors have a total area coverage of 1,000 m2 (10,760 sq. ft) and four pipe variants can cover areas of 2,000 m2 (21,520 sq. ft).
EN54-20 Aspirating Smoke Detection Sensitivity Classes
Aspirating Smoke Detection (ASD) sensitivity classes categorise systems based on their ability to detect smoke concentrations. Class A offers the highest sensitivity, Class B is normal sensitivity and Class C, with reduced sensitivity. These sensitivity classes ensure that ASD systems are tailored to specific applications, providing early smoke detection in critical areas while minimising false alarms in less demanding environments. Choosing the right class depends on the location’s unique requirements for fire safety.
In order to achieve the required class, a maximum number of sampling holes applies (pipe calculations should be carried out in order to determine the exact sensitivity):
Class A | VEP-A00-1P: 30 VEP-A00-P: 40 VEP-A10-P: 40 |
Class B | VEP-A00-1P: 40 VEP-A00-P: 80 VEP-A10-P: 80 |
Class C | VEP-A00-1P: 45 VEP-A00-P: 100 VEP-A10-P: 100 |
Pipe Lengths
VESDA-E VEP is equipped with a powerful aspirator that enables use of a total of 100m of sampling pipe in the one pipe model and 280m of pipe in the four pipe model.
VEP-A00-1P, VESDA-E VEP with LEDs, 1 Pipe, 1 Area Aspirating Smoke Detector | 1 Pipe: 100m |
VEP-A00-P, VESDA-E VEP with LEDs, 4 Pipe, 1 Area Aspirating Smoke Detector VEP-A10-P, VESDA-E VEP with 3.5″ Display, 4 Pipe, 1 Area Aspirating Smoke Detector | 1 Pipe: 110 2 Pipes: 100 3 Pipes: 80 4 Pipes: 70 |
Flair Detection Technology
Flair Detection Technology uses direct imaging of the sampled particles using a CMOS imager combined with multiple photo-diodes. This allows better detection and fewer nuisance alarms.
Orientation
VESDA-E VEP Aspirating Smoke Detectors can be inverted if the pipe network requires that the sampling pipes enter the detector at the bottom. The fascia of the detector can also be inverted so the user interface has the correct orientation.
Indication
The VESDA-E VEP-A00 detector features a range of LED Indicators to indicate Alert, Action, Fire 1, Fire 2, Disabled, Fault and Power.
VESDA-E VEP A10 detectors have a built-in 3.5″ touch screen that provides a range of status information, accessible via a series of screens.
VESDAnet
VESDAnet is a bidirectional data communication network between connected VESDA-E devices. The VESDAnet network allows VESDA-E VEP detectors to report alarms and faults to a fire panel using a remote display module, remote relay module or HLI. It also allows configuration and monitoring of devices from a central computer and connection to a reference detector.
Backward Compatibility
VESDA-E VEP is fully compatible with existing VESDA installations and occupies the same pipe, conduit, mounting footprint and electrical positioning as VESDA VLP. VESDA-E VEP detectors are also compatible with existing VESDAnet installations, allowing both VESDA-E and legacy detectors to be monitored via the latest iVESDA application.
Turntable
Approvals
VESDA-E VEP Aspirating Smoke Detectors are fully approved by VdS for safe use and installation in any European Union country and bear the CE mark to show that they comply with all the applicable directives including the CPR, EMC and the Low Voltage Directive (LVD).
EN54-20:2006 + AC:2008 – Fire detection and fire alarm systems – Control and indicating equipment.
Tech Specs
Supply Voltage | 18-30 Vdc (24V Nominal) |
Power Consumption @ 24Vdc | Aspirator SettingVEP-A00-1P: FixedVEP-A00-P & VEP-A10-P: 1-5 Power (Quiescent)VEP-A00-1P: 8.8wVEP-A00-P: 7.0 – 8.8wVEP-A10-P: 8.2w – 10.0w Power (In Alarm)VEP-A00-1P: 9.6wVEP-A00-P: 7.8w – 9.6wVEP-A10-P: 10.4w – 11.6w |
Dimensions (W x H x D) | 350 mm x 225 mm x 135 mm (13.8 in x 8.9 in x 5.3 in) |
Weight | VEP-A00-1P: 4.0 kg (8.8 lb)VEP-A00-P: 4.0 kg (8.8 lb)VEP-A10-P: 4.1 kg (9.0 lb) |
Operating Conditions | Ambient: 0°C to 39°C (32°F to 102°F)Sampled Air: -20°C to 60°C (-4°F to 140°F)Tested to: -20°C to 55°C (-4°F to 131°F), UL: -20°C to 50°C (-4°F to 122°F)Humidity: 10% to 95% RH, non-condensing |
Area Coverage | VEP-A00-1P: 1,000m2 (10,760 sq.ft)VEP-A00-P & VEP-A10-P: 2,000m2 (21,520 sq.ft) |
Minimum airflow per pipe | 15 l/m |
Pipe Length (Linear) | VEP-A00-1P: 100 m (328ft)VEP-A00-P & VEP-A10-P: 280 m (919ft) |
Pipe Length (Branched) | VEP-A00-1P: 130m (427ft)VEP-A00-P & VEP-A10-P: 560m (1,837ft) |
Pipe lengths depending on number of pipes in use | VEP-A00-1P: 100m (328ft) VEP-A00-P & VEP-A10-P1 Pipe: 110m (361ft)2 Pipe: 100m (328ft)3 Pipes: 80m (262ft)4 Pipes: 70m (230ft) |
Number of Holes | VEP-A00-1PClass A: 30Class B: 40Class C: 45 VEP-A00-P & VEP-A10-PClass A: 40Class B: 80Class C: 100 |
Computer Design Tool | ASPIRE |
Pipe | Inlet: External diameter 25mm or 1.05in (3/4in IPS)Exhaust: External diameter 25mm or 1.05in (3/4in IPS) via adaptor |
Relays | 7 programmable relays (latching or non-latching states)Contacts rated 2A @ 30Vdc (Resistive) |
IP Rating | IP40 |
Cable Access | 4 x 26mm (1.02in) cable entries |
Cable Termination | Screw terminal blocks 0.2–2.5sq mm (24–14 AWG) |
Dynamic Range | 0.001% to 32% obs/m (0.0003% to 10% obs/ft) |
Sensitivity Range | 0.005 to 20% obs/m (0.0016% to 6.25% obs/ft) |
Threshold Setting Range | Alert: 0.005% to 2.0% obs/m (0.0016% to 0.625% obs/ft)Action: 0.005% to 2.0% obs/m (0.0016% to 0.625% obs/ft)Fire 1: 0.010% to 2.0% obs/m (0.0031% to 0.625% obs/ft)Fire 2: 0.020% to 20.0% obs/m (0.0063% to 6.25% obs/ft) |
Software Features | Event log: Up to 20,000 events Smoke level, user actions, alarms and faults with time and date stamp AutoLearn: Detector learns Alarm Thresholds and Flow Fault thresholds by monitoring the environment |
Downloads
Datasheet
Manuals
Specifications
Approvals
- VESDA-E VEP Certificate of Constancy of Performance
- VESDA-E VEP VdS Certificate
- VESDA-E VEP UL Certificate
- VESDA-E VEP FM Certificate
- VESDA-E VEP EU Declaration of Conformity
- VESDA-E VEP Declaration of Performance
Buy
Eurofyre is an authorised distributor of Honeywell and has been a major technical wholesaler of Xtralis products since 2007. We offer expert advice and supply all aspects of VESDA, FAAST and ICAM aspirating smoke detection systems including pipework calculations, demonstration/training and excellent after-sale support.