Key Features
- Permissible temperature range: –30 °C to +60 °C
- Immune to disturbances such as dust, dirt, moisture and steam
- Reliable detection in difficult environments
- Protection against false alarms
- Simple to integrate into existing architecture
Overview
The Securiton ASD 531 is an advanced air sampling smoke detector designed for reliable early fire detection. It is suitable for smaller areas where fast and precise detection is crucial. The system works by continuously drawing air from the protected area through a network of pipes into the detection unit, where it is analysed for smoke particles.
The Securiton ASD 531 is known for its ease of installation, configuration and maintenance, making it ideal for applications in environments such as data centres, archives and high-risk areas where traditional smoke detectors may not be effective.
Area Coverage
The Securiton ASD 531 provides efficient smoke detection coverage for areas up to 720m², with a maximum pipe length of 40 metres. It is ideal for small to medium-sized spaces, ensuring rapid detection and response in environments like server rooms, archives, and critical infrastructure.
EN54-20 Aspirating Smoke Detection Sensitivity Classes
The Securiton ASD 531 offers three sensitivity classes to cater to different detection needs:
- Class A (Very High Sensitivity) for environments requiring early detection of the smallest smoke particles, such as clean rooms and data centres;
- Class B (High Sensitivity) for areas like museums and libraries, where asset protection from smoke damage is crucial; and
- Class C (Standard Sensitivity) for general applications, including offices and public buildings, providing reliable smoke detection while minimising false alarms.
Each class allows precise configuration to suit the specific conditions of the monitored area.
Sensitivity Class | Number of Sampling Apertures |
Class A | 6 |
Class B | 8 |
Class C | 12 |
Pipe Lengths
The Securiton ASD 531 supports sampling pipe configurations in various shapes, including I, U, T, H, and E.
Orientation
The Securiton ASD 531 can be rotated so that the pipe inlets can exit towards the ground or from the top to the ceiling.
Indication
The ASD 531 offers a standard LED display with Alarm, Fault and dusty or dirty indication, and a reset and power button.
Turntable
Approvals
VdS, FM, UL, UKCA, and CE are certifications marking compliance with safety and quality standards globally. VdS and FM focus on fire safety, UL offers broad safety certifications, UKCA signifies UK standards post-Brexit, and CE indicates a product meets essential EU health, safety and environmental requirements.
Tech Specs
Supply voltage range | 14 to 30 (UL/FM = 16.4 bis 27) VDC |
Sampling pipe diameter, typical (inner/outer) | Ø 20 / 25 mm |
Response range | EN 54-20, Class A, B, C |
Max. loading capacity, relay contact | 50 (UL max. 30) VDC1 A30 W |
Switch-on current peak (caused by EMC protection elements on the ASD supply input) | approx. 5 A for max. 1 mx |
Sampling hole diameter | Ø 2 / 2.5 / 3 / 3.5 / 4 / 4.5 / 5 / 5.5 / 6 / 6.5 / 7 mm |
Max. loading capacity per OC output (dielectric strength 30 VDC) | 100 mA |
Dimensions ASD 531 (W x H x D) | 195 x 333 x 140mm |
Weight ASD 5321 (incl. SSD 532-x) | 2,000g |
Downloads
Datasheet
Brochure
Manuals
Approvals
- Securiton ASD 531 Certificate of Constancy of Performance
- Securiton ASD 531 VdS Certificate
- Securiton ASD 531 FM Certificate
- Securiton ASD 531 UL Certificate
- Securiton ASD 531 Declaration of Conformity
- Securiton ASD 531 Declaration of Performance
Buy